Networking; Foc Networking With Phoenix Contact - Psi-Mos-Dnet Can/Fo - Bosch FPA-5000 Product Information

Modular fire panel
Hide thumbs Also See for FPA-5000:
Table of Contents

Advertisement

Modular Fire Panel
The cable set is also usually required when a second battery pack is connected.
Cable length: 180 cm
CPP 0000 A Cable Set HPD/UPS
This cable connects a UPS 2416 A Universal Power Supply used especially for an NAC line to
the HPD 0000 A Power Distributor. Cable length: 120 cm (47 inches)
CPA 0000 A Cable Set AT 2000
This two-part cable set connects the panel with the AT 2000 transmission device. The cable
with the RS232 connectors is only required for the optional TeleService and connects the AT
2000 directly to the MPC-xxxx-B Panel Controller. The other cable connects the AT 2000 to
the ENO 0000 B Fire Service Interface Module.
1.18

Networking

Up to 32 panel controllers and/or remote keypads can be combined to form a network using
their CAN interfaces.
Depending on the application, different panel controllers and remote keypads can be divided
into groups and defined as network nodes or local nodes. As a rule, within any given group,
only the status of control panels within the defined group can be displayed. The status of all
control panels can be displayed and/or processed from network nodes, irrespective of the
group to which the panels belong. Local nodes display the status of their associated control
panels. The following three topologies can be used for networking via the CAN1 and CAN2
interfaces:
The rules that must be applied for network configuration can be found in
Section 3.13 Networking rules.
1.18.1

FOC networking with Phoenix Contact - PSI-MOS-DNET CAN/FO

Networking can also be carried out using fiber optic cables. The PSI-MOS-DNET CAN/FO
Phoenix Contact CAN/FOC converters enable connection between up to 32 panel controllers.
The maximum distance between two panel controllers here is 700 m (2296 feet).
For details on structure and configuration, please read the following technical information
document: FPA 5000 network via fiber-optics converters "Phoenix Contact - PSI-MOS-DNET
CAN/FO", which you can find on the Bosch Security Systems Extranet at http://
www.boschbest.de.
Bosch Sicherheitssysteme GmbH
Non-redundant bus via CAN1
Redundantly via the CAN1 and CAN2 buses
Redundantly via CAN1 and CAN2 as a loop
Product Information
Product Description | en
51
F.01U.028.089 | 5.4 | 2009.08