en | Installation/Configuration Notes
3.6
System limiting values
General system limiting values
Control panels/remote keypads in the network
- Loop topology
- Bus topology, redundant
- Bus topology, non-redundant
Addresses
- Standalone control panel
- In the network, total
- In the network, per control panel
Detection points/detector groups
- Standalone control panel
- In the network, total
- In the network, per control panel
System limiting values per fire panel
Lists, e.g. bypass group
Total modules per panel
Printers
Alarm counters (external, internal, testing)
Entries in the event database
Event entries in the event database from release 2.1
FSP-5000-RPS Programming Interfaces
Time control channels
Time control programs
Programming a specific day
User profiles
Access levels
For installation reasons, only 42 modules can be programmed when configuring a redundant
control panel. It is possible to have 46 modules per panel without redundancy if 1 housing
with the panel controller and 10 modules plus three housings with 12 modules each are
installed.
With redundancy, the redundant panel controller is installed in the fourth housing. In addition,
because the short panel rail (with two module slots) cannot be used, the fourth housing only
provides eight module slots (see also Section 3.11 Redundancy).
NOTICE!
For systems conforming to EN 54-2, a redundant panel controller must be used when more
than 512 detectors are connected.
3.7
System limiting values of functional modules
CTN
BCM-0000-B
CZM 0004 A
F.01U.028.089 | 5.4 | 2009.08
Functional module
Battery Controller Module
CZM 0004 A 4 Zone Conventional Module
Product Information
Modular Fire Panel
Max. number
32
8
8
4096
32,512
2032
4096
32,512
2032
Max. number
128
46
4
3
1000
10,000
1
20
19
365
10
4
Max. number
8
32
Bosch Sicherheitssysteme GmbH