Table 3.9 Commander SE Size 2, 400V Three phase units
AC supply voltage and frequency
Input displacement factor (cos φ)
Nominal motor power - kW
Nominal motor power - HP
Output voltage and frequency
100% RMS output current - A
150% overload current for 60 secs - A
Typical full load input current - A*400V, 50Hz/480V, 60Hz
Typical inrush current - A** (duration <10ms)
Drive power losses at 480VAC at 6kHz switching
frequency - W
Weight - kg/lb
Cooling fan fitted
* See section 3.1.1.
** For an explanation of inrush current, see section 3.1.2.
Table 3.10 Recommended fuses and cables
Recommended input supply fuse - A
Control cable
Recommended input cable
Recommended motor cable
Recommended braking resistor cable
Table 3.11 Braking Resistors
Minimum braking resistor value - Ω
Recommended braking resistor value - Ω
Maximum braking current - A
Resistor peak power rating - kW
Before fitting a braking resistor please read the information on Braking, and
NOTE
the Warnings on High Temperatures and Overload Protection at the end of
this section.
Commander SE User Guide
Issue Number 5
MODEL
MODEL
mm²
AWG
mm²
AWG
mm²
AWG
mm²
AWG
MODEL
SE23400...
075
110
150
220
3 phase 380 to 480V +/- 10%, 48 to 62Hz
>0.97
0.75
1.1
1.5
2.2
1.0
2.0
3.0
3 phase, 0 to input voltage, 0 to 1000Hz
2.1
3.0
4.2
5.8
3.2
4.5
6.3
8.7
3.6
4.8
6.4
9.3
90
43
57
77
97
2.75 / 6
No
Yes
SE23400...
075
110
150
220
10
16
≥ 0.5
20
1.0
1.5
16
14
1.0
16
1.5
14
SE23400...
075
110
150
220
100
200
10
12.5
3.4
300
400
3.0
4.0
5.0
7.6
9.5
11.4
14.3
11
14
60
122
158
300
400
20
2.5
12
1.5
14
300
400
75
100
6.9
9
Need help?