Fig. 6.4-2 Mains Connection 230/240 V 0.25; Power Connections For 230 V Mains Voltage - Lenze 8200 vector System Manual

0.25 kw...90 kw
Hide thumbs Also See for 8200 vector:
Table of Contents

Advertisement

Show/Hide Bookmarks
6
6.4
6.4.2
6.4.2

Power connections for 230 V mains voltage

Mains connection 230/240 V
8200 vector 0.25 ... 2.2 kW
6.4-4
( ( ( (
Stop!
Controller type E82EVxxxK 2 C must only be connected to a
l
mains voltage of 1/N/PE AC 180 ... 264 V or 3/PE AC 100 ...
264 V. Higher mains voltages will destroy the controller!
The discharge current to PE is > 3.5 mA. EN 50178 requires a
l
fixed installation. Double PE connection required.
E82EV251K2B
E82EV371K2B
X1.1
L1
PE
L2/N
L1
N
PE
1/N/PE AC 230 V/240 V
E82EV551K2B
E82EV751K2B
L1
L3 PE
X1.1
+UG -UG
L2/N
L1
N
PE
1/N/PE AC 230 V/240 V
E82EV152K2B
E82EV222K2B
+UG -UG
L1
L1
L2/N L3/N
X1.1
1.5 mm
2
1.5 mm
2
2
2
2.5 mm
2.5 mm
2.5 mm
L1
N
1/N/PE AC 230 V/240 V
Fig. 6.4-2
Mains connection 230/240 V 0.25 ... 2.2 kW
0
Use two separate cables 1.5 mm
X1.1/+UG,
DC supply (DC-bus operation - see Operating Instructions)
X1.1/-UG
E82EV222K2C
Operation only with mains choke
EDS82EV903-1.0-11/2002
Basic unit wiring
Basic units in the power range 0.25 ... 2.2 kW
Power connections for 230 V mains voltage
L1
PE
L2/N
L1
L2
PE
2/PE AC 230 V/240 V
L1
L3 PE
+UG -UG
L2/N
L1 L2
PE
2/PE AC 230 V/240 V
PE
+UG -UG
L1
L1
L2/N L3/N
PE
1.5 mm
2
1.5 mm
2
2
2
2
2
2.5 mm
2.5 mm
2.5 mm
L1
L2
PE
PE
2/PE AC 230 V/240 V
2
to connect the terminals!
L1
L3 PE
+UG -UG
L2/N
L1 L2
L3
PE
3/PE AC 230 V/240 V
+UG -UG
L1
L1
L2/N L3/N
PE
L1
L2
L3
PE
3/PE AC 230 V/240 V
8200vec012