Electrical installation

Mains connection

Connection plan for controllers type E82xVxxxK2C (230/240 V mains)

Mains connection
Connection plan for controllers type E82xVxxxK2C (230/240 V mains)
(
Stop!
Only connect the controller to the permitted mains voltage (^ Technical data). A
ƒ
higher mains voltage destroys the controller!
Some controllers may only be actuated with a mains choke or mains filter. This
ƒ
requirement can differ with regard to operation at rated power and operation at an
increased rated power.
The leakage current to earth (PE) is > 3.5 mA. In accordance with EN 61800−5−1 a
ƒ
fixed installation is required. The PE conductor has to be designed double.
E82EV251K2C
E82EV371K2C
L1
PE
L2/N
X1.1
L1
N
PE
1/N/PE AC 230 V/240 V
E82EV551K2C
E82EV751K2C
L1
L3 PE
+UG -UG
L2/N
X1.1
L1
N
1/N/PE AC 230 V/240 V
E82EV152K2C
E82EV222K2C
L1
L1
+UG -UG
L2/N L3/N
X1.1
1.5 mm
2
0
1.5 mm
2
2.5 mm
2.5 mm
L1
1/N/PE AC 230 V/240 V
0
Route two cables with 1.5 mm
X1.1/+UG, X1.1/−UG
Supply for DC−bus operation
120
L1
PE
L2/N
L1
L2
PE
2/PE AC 230 V/240 V
L1
L3 PE
+UG -UG
L2/N
PE
L1 L2
PE
2/PE AC 230 V/240 V
PE
L1
L1
+UG -UG
L2/N L3/N
2
1.5 mm
2
0
1.5 mm
2
2
2
2
2
2.5 mm
2.5 mm
2.5 mm
2.5 mm
L1
L2
N
PE
2/PE AC 230 V/240 V
L1
L3 PE
+UG -UG
L2/N
L1 L2
L3
PE
3/PE AC 230 V/240 V
PE
L1
L1
PE
+UG -UG
L2/N L3/N
2
L1
L2
L3
PE
PE
3/PE AC 230 V/240 V
2
each to the terminals!
l
8200vec012
EDK82EV222 DE/EN/FR 13.0