Application Examples

7 Application Examples
The examples in this section are intended as a quick
reference for common applications.
Parameter settings are the regional default values
unless otherwise indicated (selected in
parameter 0-03 Regional Settings).
Parameters associated with the terminals and
their settings are shown next to the drawings.
Required switch settings for analog terminals 53
or 54 are also shown.
NOTICE
When the STO feature is not used, a jumper wire is
required between terminals 12, 37, and 38 for the
7
7
frequency converter to operate with factory default
programming values.
7.1.1 AMA
FC
+24 V
12
+24 V
13
18
D IN
D IN
19
D IN
27
D IN
29
D IN
32
33
D IN
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
Table 7.1 AMA with T27 Connected
38
®
VLT
Midi Drive FC 280
Parameters
Function
Setting
Parameter 1-29 A
[1] Enable
utomatic Motor
complete
Adaptation
AMA
(AMA)
Parameter 5-12 T
*[2] Coast
erminal 27
inverse
Digital Input
*=Default value
Notes/comments: Set
parameter group 1-2* Motor
Data according to motor
specifications.
NOTICE
If terminal 12 and 27 are
not connected, set
parameter 5-12 Terminal 27
Digital Input to [0] No
operation.
Danfoss A/S © 11/2015 All rights reserved.
7.1.2 Speed
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
D IN
27
D IN
29
D IN
32
D IN
33
+10 V
50
+
A IN
53
A IN
54
COM
55
-
A OUT
42
0 ~10 V
Table 7.2 Analog Speed Reference (Voltage)
FC
+24 V
12
+24 V
13
18
D IN
D IN
19
D IN
27
D IN
29
D IN
32
D IN
33
+10 V
50
+
A IN
53
A IN
54
COM
55
-
A OUT
42
4 - 20mA
Table 7.3 Analog Speed Reference (Current)
Parameters
Function
Setting
Parameter 6-10 T
erminal 53 Low
0.07 V*
Voltage
Parameter 6-11 T
erminal 53 High
10 V*
Voltage
Parameter 6-14 T
erminal 53 Low
0
Ref./Feedb. Value
Parameter 6-15 T
erminal 53 High
50
Ref./Feedb. Value
Parameter 6-19 T
[1] Voltage
erminal 53 mode
*=Default value
Notes/comments:
Parameters
Function
Setting
Parameter 6-12 T
erminal 53 Low
4 mA*
Current
Parameter 6-13 T
erminal 53 High
20 mA*
Current
Parameter 6-14 T
erminal 53 Low
0
Ref./Feedb. Value
Parameter 6-15 T
erminal 53 High
50
Ref./Feedb. Value
Parameter 6-19 T
[0] current
erminal 53 mode
*=Default value
Notes/comments:
MG07A102