Commissioning
1
A
Setup 1
2
Status
4
B
Menu
9
C
On
OK
6
Warn
Alarm
8
O
Hand
D
Reset
On
13
Illustration 5.1 View of the LCP
A. Numeric display
The LCD-display is back-lit with 1 numeric line. All data is
shown in the LCP.
1
The set-up number shows the active set-up and the edit
set-up. If the same set-up acts as both active and edit set-
up, only that set-up number is shown (factory setting).
When active and edit set-up differ, both numbers are
shown in the display (for example, set-up 12). The number
flashing indicates the edit set-up.
2
Parameter number.
3
Parameter value.
4
Motor direction is shown in the bottom left of the display.
A small arrow indicates the direction, either clockwise or
counterclockwise.
5
The triangle indicates whether the LCP is in Status, Quick
Menu, or Main Menu.
Table 5.1 Legend to Illustration 5.1, Section A
Setup 12
n1
p5
p4
INDEX
p3
Illustration 5.2 Display Information
MG07A102
Operating Instructions
3
5
Quick
Main
10
Menu
Menu
11
12
10
Auto
On
14
15
AHP
VkW
srpm
Hz%
n2
n3
p2
p1
Danfoss A/S © 11/2015 All rights reserved.
B. Menu key
To select between Status, Quick Menu, or Main Menu,
press [Menu].
C. Navigation keys and indicator lights (LEDs)
Key
Function
9 [Back]
For moving to the previous step or layer
in the navigation structure.
1
For switching between parameter
Arrows [
] [
]
0
groups, parameters, and within
parameters, or increasing/decreasing
parameter values. Arrows can also be
used for setting local reference.
1
[OK]
Press to access parameter groups or to
1
enable a selection.
1
Press to move from left to right within
[►]
2
the parameter value to change each
digit individually.
Table 5.2 Legend to Illustration 5.1, Navigation Keys
Indicator Light
Function
6
On
Green
ON turns on when the frequency
converter receives power from the
mains voltage, a DC bus terminal, or a
24 V external supply.
7
Warn
Yellow When warning conditions are met, the
yellow WARN light turns on and text
appears in the display area identifying
the problem.
8
Alarm
Red
A fault condition causes the red alarm
light to flash and an alarm text is
shown.
Table 5.3 Legend to Illustration 5.1, Indicator Lights (LEDs)
D. Operation keys and indicator lights (LEDs)
Key
Function
13 Hand On
Starts the frequency converter in local control.
An external stop signal by control input or
serial communication overrides the local
hand on.
14 Off/Reset
Stops the motor but does not remove power
to the frequency converter, or resets the
frequency converter manually after a fault has
been cleared.
15 Auto On
Puts the system in remote operational mode.
Responds to an external start command by
control terminals or serial communication.
Table 5.4 Legend to Illustration 5.1, Section D