Application Examples

6 Application Examples

6.1 Introduction

NOTE
A jumper wire may be required between terminal 12 (or
13) and terminal 37 for the frequency converter to operate
when using factory default programming values.
The examples in this section are intended as a quick
reference for common applications.
Parameter settings are the regional default values
unless otherwise indicated (selected in
0-03 Regional Settings)
Parameters associated with the terminals and
their settings are shown next to the drawings
Where switch settings for analog terminals A53 or
A54 are required, these are also shown
6.2 Application Examples
CAUTION
Thermistors must use reinforced or double insulation to
meet PELV insulation requirements.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.1 AMA with T27 Connected
®
VLT
Automation Drive D-Frame
Operating Instructions
Parameters
Function
Setting
1-29 Automatic
Motor
[1] Enable
Adaptation
complete
(AMA)
AMA
5-12 Terminal 27
[2]* Coast
Digital Input
inverse
*=Default Value
Notes/comments: Parameter
group 1-2* Motor Data must be
set according to motor
®
MG34U202 - VLT
is a registered Danfoss trademark
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.2 AMA without T27 Connected
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
+
A IN
53
A IN
54
COM
55
-
A OUT
42
-10 - +10V
COM
39
U - I
A53
Table 6.3 Analog Speed Reference (Voltage)
Parameters
Function
Setting
1-29 Automatic
Motor
[1] Enable
Adaptation
complete
(AMA)
AMA
5-12 Terminal 27
[0] No
Digital Input
operation
*=Default Value
Notes/comments: Parameter
group 1-2* Motor Data must be
set according to motor
Parameters
Function
Setting
6-10 Terminal 53
Low Voltage
0.07 V*
6-11 Terminal 53
10 V*
High Voltage
6-14 Terminal 53
0 RPM
Low Ref./Feedb.
Value
6-15 Terminal 53
1500 RPM
High Ref./Feedb.
Value
*=Default Value
Notes/comments: