Application Examples
FC
+24 V
12
13
+24 V
D IN
18
D IN
19
D IN
27
D IN
29
D IN
32
D IN
33
+10 V
50
A IN
≈ 5kΩ
53
A IN
54
COM
55
A OUT
42
Table 7.4 Speed Reference (Using a Manual Potentiometer)
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
D IN
27
D IN
29
D IN
32
D IN
33
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
Table 7.5 Speed Up/Speed Down
MG07A102
Operating Instructions
Parameters
Function
Setting
Parameter 6-10 T
erminal 53 Low
0.07 V*
Voltage
Parameter 6-11 T
erminal 53 High
10 V*
Voltage
Parameter 6-14 T
erminal 53 Low
0
Ref./Feedb. Value
Parameter 6-15 T
erminal 53 High
50
Ref./Feedb. Value
Parameter 6-19 T
[1] voltage
erminal 53 mode
*=Default value
Notes/comments:
Parameters
Function
Setting
Parameter 5-10 T
erminal 18
*[8] Start
Digital Input
Parameter 5-12 T
[19] Freeze
erminal 27
Reference
Digital Input
Parameter 5-13 T
[21] Speed Up
erminal 29
Digital Input
Parameter 5-14 T
[22] Speed
erminal 32
Down
Digital Input
*=Default value
Notes/comments:
Danfoss A/S © 11/2015 All rights reserved.
Speed
Reference
Start ( 18)
Freeze ref ( 27)
Speed up ( 29 )
Speed down ( 32 )
Illustration 7.1 Speed Up/Speed Down
7.1.3 Start/Stop
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
D IN
27
D IN
29
D IN
32
D IN
33
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
Table 7.6 Start/Stop with Reversing and 4 Preset Speeds
Parameters
Function
Setting
Parameter 5-10 Ter
minal 18 Digital
[8] Start
Input
Parameter 5-11 Ter
*[10]
minal 19 Digital
Reversing
Input
Parameter 5-12 Ter
[0] No
minal 27 Digital
operation
Input
Parameter 5-14 Ter
[16] Preset
minal 32 Digital
ref bit 0
Input
Parameter 5-15 Ter
[17] Preset
minal 33 Digital
ref bit 1
Input
Parameter 3-10 Pre
set Reference
Preset ref. 0
25%
Preset ref. 1
50%
Preset ref. 2
75%
Preset ref. 3
100%
* = Default value
Notes/comments: