Application Examples
7.1.4 External Alarm Reset
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
D IN
27
D IN
29
D IN
32
D IN
33
+10 V
50
A IN
53
A IN
54
7
7
COM
55
A OUT
42
Table 7.7 External Alarm Reset
7.1.5 Motor Thermistor
NOTICE
To meet PELV insulation requirements, use reinforced or
double insulation on the thermistors.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
D IN
27
D IN
29
D IN
32
D IN
33
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
Table 7.8 Motor Thermistor
40
®
VLT
Midi Drive FC 280
Parameters
Function
Setting
Parameter 5-11 T
erminal 19
[1] Reset
Digital Input
*=Default value
Notes/comments:
Parameters
Function
Setting
Parameter 1-90
[2] Thermistor
Motor Thermal
trip
Protection
Parameter 1-93 T
[1] Analog
hermistor Source
input 53
Parameter 6-19 T
erminal 53 mode [1] Voltage
* = Default value
Notes/comments:
If only a warning is needed, set
parameter 1-90 Motor Thermal
Protection to [1] Thermistor
warning.
Danfoss A/S © 11/2015 All rights reserved.
7.1.6 SLC
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
D IN
27
D IN
29
D IN
32
D IN
33
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
01
02
03
Table 7.9 Using SLC to Set a Relay
Parameters
Function
Setting
Parameter 4-30
Motor Feedback
[1] Warning
Loss Function
Parameter 4-31
Motor Feedback
50
Speed Error
Parameter 4-32
Motor Feedback
5 s
Loss Timeout
Parameter 7-00 S
[1] 24V
peed PID
encoder
Feedback Source
Parameter 5-70 T
erm 32/33 Pulses
1024*
Per Revolution
Parameter 13-00
SL Controller
[1] On
Mode
Parameter 13-01
[19] Warning
Start Event
Parameter 13-02
[44] Reset key
Stop Event
Parameter 13-10
[21] Warning
Comparator
no.
Operand
Parameter 13-11
Comparator
*[1] ≈
Operator
Parameter 13-12
Comparator
61
Value
Parameter 13-51
[22]
SL Controller
Comparator 0
Event
Parameter 13-52
[32] Set
SL Controller
digital out A
Action
low
Parameter 5-40 F
[80] SL digital
unction Relay
output A
* = Default value
Notes/comments:
If the limit in the feedback
monitor is exceeded, warning
61, feedback monitor is issued.
The SLC monitors warning 61,
feedback monitor. If warning 61,
feedback monitor becomes true,
relay 1 is triggered.
External equipment could
indicate that service is required.
If the feedback error goes
below the limit again within 5
s, the frequency converter
continues and the warning
disappears. But relay 1 persists
until [Off/Reset] is pressed.
MG07A102