Siemens SIMATIC CFU Commissioning Manual page 176

Distributed i/o
Hide thumbs Also See for SIMATIC CFU:
Table of Contents

Advertisement

Technical specifications
12.4 Technical specifications of the Compact Field Unit DIQ
Article number
Cable length
● shielded, max.
● unshielded, max.
Digital outputs
Type of digital output
Number of digital outputs
Current-sinking
Current-sourcing
Short-circuit protection
● Response threshold, typ.
Limitation of inductive shutdown voltage to
Controlling a digital input
Switching capacity of the outputs
● on lamp load, max.
Load resistance range
● lower limit
● upper limit
Output voltage
● Type of output voltage
● for signal "1", min.
Output current
● for signal "1" rated value
● for signal "0" residual current, max.
Output delay with resistive load
● "0" to "1", max.
● "1" to "0", max.
Parallel switching of two outputs
● for uprating
● for redundant control of a load
Switching frequency
● with resistive load, max.
● with inductive load, max.
● on lamp load, max.
Total current of the outputs
● Current per channel, max.
horizontal installation
vertical installation
Cable length
● shielded, max.
176
up to 60 °C, max.
up to 70 °C, max.
up to 60 °C, max.
6ES7655-5PX31-1XX0
1 000 m
600 m
Transistor
16
No
Yes
Yes
0.7 to 1.3 A
Typ. L+ (-50 V)
Yes
5 W
48 Ω
12 kΩ
DC
Ue minus 1 V
0.5 A
0.1 mA
50 µs
100 µs
No
No
100 Hz
2 Hz
10 Hz
0.5 A
5 A
4 A
5 A
1 000 m
Commissioning Manual, 08/2019, A5E39252870-AD
SIMATIC CFU

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents