Secure Access to the System

Types of Modules

Standard Modules
FLEX 5000
I/O
TM
POWER
STATUS
5094-IB16
DIGITAL 16 INPUT 24 VDC
1
1 TB3
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Safety Modules
FLEX 5000
I/O
TM
POWER
STATUS
5094-IB16S
SAFETY DIGITAL 16 INPUT 24 VDC
5
5 TB3I
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
To secure access to the [device] by authorized users only, consider these options:
• Password helps protect the source and execution of the control program
• Remove the key from the controller
• Deploy EtherNet/IP devices in accordance with recommended
architectures and concepts. See the Converged Plantwide Ethernet
(CPwE) Design and Implementation Guide, publication ENET-TD001.
• Implement physical barriers, such as locked cabinets
To secure access to the system, consider these options:
• Follow industry best practices to harden your personal computers and
servers, including anti-virus/anti-malware and application whitelisting
solutions.
The recommendations are published at the Rockwell Automation
technical support center in Knowledgebase article Rockwell Automation
Customer Hardening Guidelines, #546987. The technical support center is
available at:
https://rockwellautomation.custhelp.com/
• Develop and deploy backup and disaster recovery policies and procedures.
Test backups on a regular schedule.
• Minimize network exposure for all control system devices and systems, and
confirm that they are not accessible from the Internet.
• Locate control system networks and devices behind firewalls and isolate
them from the business network.
• Subscribe to the Rockwell Automation Security Advisory Index,
Knowledgebase article KB54102, so you have access to information about
security matters that affect Rockwell Automation products.
Table 3
describes the types of FLEX 5000 I/O modules.
Table 3 - FLEX 5000 Standard and Safety Digital I/O Modules
(1)
Cat. No.
Description
5094-IB16, 5094-IB16XT
18...32V DC 16-point, sink input module
5094-IB16S, 5094-IB16SXT
18...32V DC 16-point sinking safety input module
5094-OB16, 5094-OB16XT
18...32V DC 16-point, sourcing output module
5094-OB16S, 5094-OB16SXT
18...32V DC 16-point sourcing safety output module
5094-OW8I, 5094-OW8IXT
5...240V AC /125V DC 8-point, isolated normally open relay output module
(1) XT modules can operate in extreme environments while non-XT modules cannot.