14. Protection Control

(For A9/12PK)

14.1 Restart Control (Time Delay Safety Control)

When the thermo-off temperature (temperature which compressor stops to operate) is reached during: -
Cooling/Heating operation - the compressor stops for 3 minutes (minimum) before resume operation.
o
Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
o
If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the
moment operation stop, although the unit is turn on again within the period.
This phenomenon is to balance the pressure inside the refrigerant cycle.

14.2 7 Minutes Time Save Control

The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls
between the compressor ON temperature and compressor OFF temperature during the period.
This phenomenon is to reduce the built up humidity inside a room.

14.3 60 Seconds Forced Operation

Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation
although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the
OFF/ON operation button at the remote control is permitted.
The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full
cycle and return back to the outdoor unit.

14.4 Starting Current Control

When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor
will start to operate at 1.6 second later.
The reason of the difference is to reduce the starting current flow.

14.5 Freeze Prevention Control

To protect indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form return to
compressor.
This control will activate when the temperature of indoor heat exchanger falls below 2°C continuously for more
than 4 minutes.
The current fan speed will change to freeze prevention speed after 70 seconds compressor on. When indoor pipe
temperature reaches certain temperature for 5 sec. the speed will be increased as in below figure.
Compressor will turn off when indoor temperature falls below 2°C for more than 4 minutes. It will restart again
when indoor heat exchanger temperature rises to 10°C.
Restart control (Time Delay Safety Control) will be applied in this control.