5

Technical daTa

5.1

Conformity

The device conforms to the EU directives as per the EU Declaration
of Conformity (if applicable).
5.2

Standards

The applied standards, which are used to demonstrate conformity
with the EU Directives, are listed in the EU type examination cer-
tificate and/or the EU Declaration of Conformity (if applicable).
8
english
Type 8652
Technical data
5.3

Operating conditions

noTe
▶ Use safety-low voltage according to protection class 3
EN 61140, VDE 0140.
Type of
permissible range
condition
Ambient
-10...+55 °C
temperature
Storage
-10...+60 °C
temperature
Altitude
Restricted to max. 2000 m above sea level
for UL approved versions
Compressed air
ISO 8573-1:2010, Class 7.4.4
quality
Nominal
Continuous operation (100% duty cycle)
operating mode
Operating
24 V
± 10%, residual ripple
voltage
for fieldbus interface 1 Vss
Protection class
3 in accordance with EN 61140, VDE 0140
UL approved Versions must be supplied by one of the following:
1)
a) Limited Energy Circuit (LEC) according to UL/ IEC 61010-1
b) Limited Power Source (LPS) according to UL/ IEC 60950
c) SELV/ PELV with UL Recognized Overcurrent Protection
dimensioned according to UL/ IEC 61010-1 Table 18
d) NEC Class 2 power source
1