SECTION 5 - TECHNICAL DATA
TABLE 9 - OPTIONAL THREE-PASS REAR INLET/FRONT OUTLET EVAPORATOR
QTC4
A
15.1
150
S
(384)
15.1
165
H
(384)
15.1
175
P
(384)
25.5
185
S
(648)
14.1
185
H
(358)
15.3
185
P
(389)
15.1
175
C
(384)
14.1
210
S
(358)
15.1
210
H
(384)
15.3
210
P
(389)
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are permitted.
Glycol limits are higher. Please contact your Quantech Sales Representative for ratings and further information.
72
ALL DIMENSIONS - INCHES (MM)
B
C
D
26.5
6.8
34.5
(673)
(173)
(876)
26.5
29.2
56.1
(673)
(742)
(1425)
26.5
34.9
70
(673)
(886)
(1778)
25.5
17.7
56.8
(648)
(450)
(1443)
25.5
61.5
56.7
(648)
(1562)
(1440)
26.7
117.3
56.1
(678)
(2979)
(1425)
26.53
1.7
38.1
(674)
(43)
(968)
25.5
61.6
58.8
(648)
(1565)
(1494)
26.5
34.9
70
(673)
(886)
(1778)
26.7
78.9
70.3
(678)
(2004)
(1786)
WATER
E
VOLUME
NOZZLE
WATER FLOW
GALLONS
SIZE
(LITERS)
58
5
(220)
58
5
(220)
71
6
(269)
48
5
(182)
48
5
(182)
58
5
(220)
71
6
(269)
48
5
(182)
71
6
(269)
71
6
(269)
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
MINIMUM
MAXIMUM
CHILLED
CHILLED
WATER
RATE
FLOW RATE
GPM (L/S)
GPM (L/S)
170 (11)
650 (41)
170 (11)
650 (41)
200 (13)
780 (49)
130 (8)
520 (33)
130 (8)
520 (33)
170 (11)
650 (41)
200 (13)
780 (49)
130 (8)
520 (33)
200 (13)
780 (49)
200 (13)
780 (49)
QUANTECH