Power Supply Wiring; Single Point Wiring; Voltage Utilization Range; Figure 13 - Single Point Power Wiring - Quantech QTC4 STYLE A Series Installation Operation & Maintenance

Air-cooled screw liquid chillers with variable speed drive, 150 - 500 tons, 525 - 1750 kw, 2 compressor, 60 hz
Hide thumbs Also See for QTC4 STYLE A Series:
Table of Contents

Advertisement

SECTION 4 - INSTALLATION

POWER SUPPLY WIRING

Minimum Circuit Ampacity (MCA),
Minimum/Maximum Fuse Size and
Minimum/Maximum Circuit Breaker size
varies on chillers based upon model and
options ordered. Consult YorkWorks or
the chiller data plate for electrical data
on a specific chiller.

FIGURE 13 - SINGLE POINT POWER WIRING

44

Single Point Wiring

Voltage Utilization Range

RATED
VOLTAGE
200/60/3
230/60/3
380/60/3
400/60/3
460/60/3
575/60/3
400/50/3
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
LD18588
UTILIZATION RANGE
180-220
208-254
342-402
360-440
414-508
520-635
360-440
QUANTECH

Advertisement

Table of Contents
loading

Table of Contents