Air-cooled inverter scroll chiller and heat pump (20 pages)
Summary of Contents for Quantech QTC3040T
Page 1
Air-Cooled Scroll Chiller Supersedes: QTC3-NM1 (1123) Form QTC3-NM1 (1223) Installation, Operation, Maintenance 035-24487-000 QTC3040T TO QTC3225T Air-Cooled Scroll Chillers with Brazed Plate Heat Exchanger Style B (60 Hz) 4 to 12 Fan 40 ton to 230 ton 140 kW to 800 kW...
Page 2
Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this warn- ing will void the manufacturer’s warranty and cause serious damage to property or personal injury. Quantech...
Page 3
Affected pages Description Updated the refrigerant warning in General safety guidelines Associated literature Manual description Form number Start-Up Checklist - Style A and B, 60 Hz 150.72-CL1 Limited Warranty Engineered Systems Equipment 50.05-NM2 Chiller A2L Refrigerant Application Data 160.00-AD10 Quantech...
Planned Service Agreement that leverages real time and generalized conditions. In lieu of the traditional and historical data, delivering performance reporting, maintenance program, a Johnson Controls Quantech corrective actions required and data enabled guidance Conditioned Based Maintenance (CBM) program can for optimal operation and lifecycle assurance.
Physical data QTC3041 to QTC3230, 60 Hz ....................50 Electrical data ..............................57 Compressor heaters ............................57 Electrical notes ............................... 72 Weight distribution and isolator mounting positions ..................106 Clearances ..............................107 Isolator locations ............................108 Isolator information ............................111 Quantech...
Page 6
Return chilled liquid system lead/lag and compressor sequencing .............. 174 Anti-recycle timer ............................174 Anti-Coincidence Timer ..........................174 Evaporator pump control and Quantech hydro kit pump control ..............174 Evaporator heater control ..........................175 Pumpdown control ............................175 Standard condenser fan control ........................175 VSD fan ................................
Introduction the contract. Quantech QTC3 chillers are manufactured to the high- The warranty is limited to parts only replacement and est design and construction standards to ensure high shipping of any faulty part, or sub-assembly, which has performance, reliability, and adaptability to all types of failed due to poor quality or manufacturing errors.
This manual and any other document supplied with the unit are the property of Quantech, which reserves all rights. They may not be reproduced, in whole or in part, without prior written authorization from an autho- rized Quantech representative.
Page 13
The use of gloves is https://my.jci.com/sites/BE/NASafety. recommended. Frame rails, brakes, and other components may also have sharp edges. Reasonable care should be taken when working in contact with any components to avoid risk of minor abrasions and lacerations. Quantech...
Page 14
Warning: Read technical manual. White, Black and Safety Orange. Warning label. Black and red symbol on white background. Refrigerant Safety Refrigerant Safety Group: A2L. Group Black and red symbol on white background. Refrigerant Safety Group: A2L. Refrigerant Safety Group Quantech...
Issue date: 12/19/2023 Section 2: Product description Introduction General system description Quantech QTC3 Air-Cooled Scroll Chillers provide Compressors chilled water for all air conditioning applications us- The chiller has suction-gas cooled, hermetic, scroll ing central station air handling or terminal units. They compressors.
• Suction pressure cutout setting • Each system suction pressure • Discharge pressure (optional) • Liquid Temperature Reset via a Quantech BAS DDC or Building Automation System (by others) using a 4 mA to 20 mA or 0 VDC to 10 VDC input...
KVA capacity). Factory mounting includes primary ing depending on model. and secondary wiring between the transformer and the control panel. (Factory-mounted) • The standard control panel can be directly con- nected to a Quantech Building Automated Sys- Control Options tem. Ambient Kit (Low) Power panel Units will operate to 30°F (-1.1°C).
Page 19
Service shut off valves, additional pressure ports and ex- • Wire/louvered panels - Consists of welded wire- pansion tanks are optional within the hydro-kit option. mesh panels on the bottom part of unit and lou- vered panels on the condenser section of the unit. (Factory-Mounted) Quantech...
Page 20
• Ultra Quiet Fans - Lower RPM, 8-pole fan mo- tors are used with steeper-pitch fans. (Factory- Mounted) Vibration isolators Level adjusting, spring type 1 in. (25.4 mm) or seismic deflection or neoprene pad isolators for mounting un- der unit base rails. (Field-mounted) Quantech...
Form QTC3-NM1 Section 1: General chiller information and safety Issue date: 12/19/2023 Item Description Item Description Fan assemblies Filter drier Condenser coils Power panel Evaporator Control panel Compressors Sight glass – – Figure 1: Unit components, front view Quantech...
Form QTC3-NM1 Section 1: General chiller information and safety Issue date: 12/19/2023 Item Description Condenser coils Fan assemblies Condenser coils Receivers Evaporator Figure 2: Unit components, side view Quantech...
Form QTC3-NM1 Section 1: General chiller information and safety Issue date: 12/19/2023 LD13248 Item Description Fan contactor Fan fuses Fan contactor Disconnect switch (optional) XTBF1 Compressor contactors Compressor overloads Figure 3: Power panel components Quantech...
Section 1: General chiller information and safety Issue date: 12/19/2023 LD13248b Item Description Fan contactor Fan fuses Control relay Microcomputer control center Display Keypad XTBC1 Microboard XTCB2 XTBF2 Compressor contactors Compressor overloads Figure 4: Power Panel and control components Quantech...
SP Circuit Breaker w/ Lockable Handle, 65 kA SCWR (PIN 16 &17) SP Circuit Breaker w/ Lockable Handle MP Supply w/Ind Sys CB&L Ext Handles No Control Transformer Required Cntrl Transformer TRANS Control Transformer Required (PIN 18) Special Control Transformer Required Quantech...
Page 26
Special Chicago Code Kit required Standard Valves Required Valves VALVES Electronic Expansion Valve (PIN 32) Special Optional Valves Required No Hot Gas Bypass required Hot Gas Bypass HGBP Hot Gas Bypass required - 1 circuit (PIN 33) Special Hot Gas Bypass required Quantech...
Page 27
End Louver (End Hail Guard) Encl Panels (factory) End Louver (End Hail Guard) Encl Panels (field) Aesthetic Panel Kit only (factory) Aesthetic Panel Kit only (field) Aesthetic Panel Kit plus Hail Guards (factory) Aesthetic Panel Kit plus Hail Guards (field) Special Enclosure Panels Quantech...
Page 28
SR Documents SRDOCS (PIN 50) Base & Material Documents Base & Witness Documents Special Quote Quantech Branding SASO Compliant Label Special Quote Standard Low Sound Fan Required Ultra Quiet Fans Required High Air Flow Fan Requied Standard Low Sound Fan with VSD Required...
Page 29
Pump Kit W Pump Kit Y Pump Kit Z No Option Single Pump, Standard Single Pump, Full Feature Pump Package Options PKGOPT Dual Pump, Standard (PIN 60) Dual Pump, Full Feature VSD Single Pump, Full Feature VSD Dual Pump, Full Feature Quantech...
Page 30
Section 1: General chiller information and safety Issue date: 12/19/2023 Table 2: Complete PIN number description, continued Feature Feature description Option Option description PIN 61 PIN 61 – Marketing purposes only Guangzhou, China Mfg Location Monterrey, Mexico San Antonio, Texas Quantech...
Low pressure vapor enters at the compres- sion valve where pressure is reduced and further cool- sor where pressure and superheat are increased. The ing takes place before entering to the cooler. Quantech...
Page 32
Form QTC3-NM1 Section 1: General chiller information and safety Issue date: 12/19/2023 This page is intentionally left blank. Quantech...
Therefore a professional rig- ger must determine the rigging and lifting method to be used and it is beyond the scope of the manual to specify rigging and lifting details. Quantech...
If the unit is to be put into storage, before installation, Major damage must be reported immediately to your the following precautions should be observed: local Quantech representative. • The chiller must be blocked so that the base is not Moving the chiller permitted to sag or bow.
Form QTC3-NM1 Section 3: Handling and storage Issue date: 12/19/2023 LD18121 LD18120 4 - 6 fan units 8 fan units LD27282 10 fan units LD27283 12 fan units Figure 7: Unit Rigging/Lifting Quantech...
The lugs are attached to the cables/chains using shack- les or safety hooks. CORRECT INCORRECT LIFTING HOLE IN BASE FRAME FLANGE FLANGE LOCKING PIN LIFTING HOLE LOCKING PIN IN BASE FRAME LOCKING FLANGE Figure 8: Lifting lugs Quantech...
In installations where winter operation is intended and ment must be commissioned and serviced snow accumulations are expected, additional height by an authorized Quantech service me- must be provided to ensure normal condenser air flow. chanic or a qualified service person expe- Do not smoke smoking or have an open flame in the rienced in chiller installation.
Hand stop valves should be installed in all lines to fa- • A chilled water flow switch, (either by Quantech cilitate servicing. or others) MUST be installed in the leaving wa- ter piping of the cooler.
AL-CU to the unit, or loss of performance, and may invalidate compression fittings should be used to transition from the warranty. aluminum to copper. This transition should be done in Quantech...
XTBC2 – Termi- be done. nals 25 to 26 for system 1, and XTBC2 – Terminals 27 to 28 for system 2. See Figure 4 on page 24, Figure 14 on page 46 and unit wiring diagram. Quantech...
LETHAL VOLTAGES are present inside and unit as a result of the chilled liquid the panel AFTER disconnecting power, freezing. before working on equipment. Figure 10: Single-Point Supply Connection – Terminal Block, Non-Fused Disconnect Switch or Circuit Breaker Quantech...
To prevent serious injury or death, the technician should verify that NO LETHAL VOLTAGES are present inside the panel AFTER disconnecting power, before working on equipment. Figure 11: Control Wiring Inputs Quantech...
< 5 No Limit Total Hardness (odH) mg/L 4.0–8.5 No Limit Nitrate (NO³-) < 100 No Limit Iron (Fe) mg/L < 0.2 No Limit Aluminum (Al) mg/L < 0.2 No Limit Manganese (Mn) mg/L < 0.1 No Limit Quantech...
3. Wiring of Thermal Dispersion Flow Switch a. The wire connection of thermal dispersion switch contains 5 pins, the central pin is Pin #5 used for programming, which is unneces- sary for wiring. See Figure 13 on page 44. Quantech...
Page 45
• Mount the thermal dispersion flow switch on the top of the horizontal pipes only if the pipe is fully filled with liquid. Mount the thermal dispersion flow switch on the bottom of the horizontal pipes only if the pipe is free from buildup. Quantech...
The unit evaporator heater uses 120 VAC. Disconnecting 120 VAC power from the unit, at or below freezing temperatures, can result in damage to the evaporator and unit as a result of the chilled liquid freezing. Figure 14: Control wiring outputs Quantech...
1. For leaving liquid temperature below 40°F (4.4°C) (to 10°F [-12.2°C]), an optional low temperature glycol kit is required. Contact your nearest Quantech Office for application requirements. 2. For leaving liquid temperature higher than 55°F (12.8°C), contact the nearest Quantech Office for application guidelines. 3. The evaporator is protected against freezing to -20°F (-28.9°C) with an electric heater as standard.
24.0 26.0 20.0 25.1 17.9 20.0 24.3 19.0 30.0 25.9 30.0 24.9 40.0 26.9 -8.1 40.0 25.6 -6.0 50.0 28.0 -28.9 50.0 26.6 -28.0 NOTE: Water Pressure Drop Curves may extend past the minimum and maximum water flow ranges. Quantech...
13.2 10.0 Maximum water side pressure, psig Maximum refrigerant side pressure, psig Minimum chiller water flow rate, gpm Maximum chiller water flow rate, gpm Water connections size, in. Note: * Standard side extension kit, evaporator nozzle remains 3 in. Quantech...
Page 51
Total chiller, cfm 26,800 60,000 60,000 60,000 60,000 90,000 Evaporator Water volume, gal Maximum water side pressure, psig Maximum refrigerant side pressure, psig Minimum chiller water flow rate, gpm Maximum chiller water flow rate, gpm Water connections size, in. Quantech...
Page 52
14.3 12.6 14.3 Maximum water side pressure, psig Maximum refrigerant side pressure, psig Minimum chiller water flow rate, gpm Maximum chiller water flow rate, gpm Water connections size, Note: * Standard side extension kit, evaporator nozzle remains 3 in. Quantech...
Page 53
13.2 10.0 Maximum water side pressure, psig Maximum refrigerant side pressure, psig Minimum chiller water flow rate, gpm Maximum chiller water flow rate, gpm Water connections size, in. Note: * Standard side extension kit, evaporator nozzle remains 3 in. Quantech...
Page 54
Water volume, gal Maximum water side pressure, psig Maximum refrigerant side pressure, psig Minimum chiller water flow rate, gpm Maximum chiller water flow rate, gpm Water connections size, in. Note: * Standard side extension kit, evaporator nozzle remains 3 in. Quantech...
Page 55
Total chiller, cfm 26800 60000 60,000 60,000 60,000 90,000 Evaporator Water volume, gal Maximum water side pressure, psig Maximum refrigerant side pressure, psig Minimum chiller water flow rate, gpm Maximum chiller water flow rate, gpm Water connections size, in. Quantech...
Page 56
14.3 12.6 14.3 Maximum water side pressure, psig Maximum refrigerant side pressure, psig Minimum chiller water flow rate, gpm Maximum chiller water flow rate, gpm Water connections size, Note: * Standard side extension kit, evaporator nozzle remains 3 in. Quantech...
70 W heaters and larger compressors use 120 compressors on start. W heaters. If power is OFF more than two hours, the crankcase heaters must be energized for 18 hours to 24 Quantech...
145.0 18.0 116.0 Note: Reference PIN 59 for Pump Model. Use this table along with Table 11 on page 59 to determine electrical data of the unit plus the pump. Table 10: Transformer Load Volt 2000 3000 14.4 13.0 Quantech...
21.5 21.5 15.3 Notes: • Reference PIN 59 for pump models. • Use this table along with Table 9 on page 58 to determine electrical data of the unit plus the pump. • Does not include the control transformer. Quantech...
Page 60
42.5 42.5 15.3 Notes: • Reference PIN 59 for pump models. • Use this table along with Table 9 on page 58 to determine electrical data of the unit plus the pump. • Does not include the control transformer. Quantech...
Page 61
51.9 51.9 15.3 Notes: • Reference PIN 59 for pump models. • Use this table along with Table 9 on page 58 to determine electrical data of the unit plus the pump. • Does not include the control transformer. Quantech...
Page 62
21.5 21.5 15.3 Notes: • Reference PIN 59 for pump models. • Use this table along with Table 9 on page 58 to determine electrical data of the unit plus the pump. • Does not include the control transformer. Quantech...
Page 63
15.3 — — Notes: • Reference PIN 59 for pump models. • Use this table along with Table 9 on page 58 to determine electrical data of the unit plus the pump. • Does not include the control transformer. Quantech...
Page 64
51.9 51.9 15.3 Notes: • Reference PIN 59 for pump models. • Use this table along with Table 9 on page 58 to determine electrical data of the unit plus the pump. • Does not include the control transformer. Quantech...
(1) 6 - 350 — (1) 6 - 350 — Note: Alternate lugs are available in the panel for field electricians and contractors, if other lug arrangements are necessary for the installed lugs on the non-fused disconnect switch and circuit breaker panels. Quantech...
Page 71
(2) 3/0 - 250 (1) 250 - 500 Note: Alternate lugs are provided in the panel for field electricians and contractors, if other lug arrangements are necessary for the installed lugs on the non-fused disconnect switch and circuit breaker panels. Quantech...
FACTORY MOUNTED CIRCUIT BREAKER -58 = 575-3-60 FULL LOAD AMPS HERTZ MAXIMUM MINIMUM CIRCUIT AMPACITY MINIMUM MIN NF MINIMUM NON FUSED RATED LOAD AMPS S.P. WIRE SINGLE POINT WIRING UNIT MTD SERV SW UNIT MOUNTED SERVICE (NON-FUSED DISCONNECT LOCKED ROTOR AMPS Quantech...
Page 73
HEATER RELAY STANDARD QUANTECH ACCESSORIES COMPRESSOR CONTACTOR WIRING AND ITEMS SHOWN THUS ARE - KM (INCLUDING COIL SUPPRESSOR) NOT SUPPLIED BY QUANTECH - KCR CONTROL RELAY ITEMS THUS ENCLOSED FORM A COMPONENTS OR SETS OF PUMP CONTACTOR PART - KP...
Page 74
All sources of supply shown on this diagram must be taken from one main isolator, not shown or supplied by Quantech Green and yellow wire is used for earth, multi-colored cable used for low voltage. Red wire used for AC Control, blue wire for neutral, black wire for AC and DC power.
Page 75
G System 3 with 5-fans - details shown on drawing - 123 Auxiliary switches for manual motor protectors Auxiliary switches for manual motor protectors for 3 compressor units only LON module option for smart chiller enclosure Smart chiller assembly Quantech...
At the top of the pages the numbers 1 to 11 go from left to right. Find drawing number 2 and in column number 1 across the top of the page, locate wire number 1. Figure 15: Elementary Wiring Diagram Quantech...
Page 78
At the top of the pages the numbers 1 to 11 go from left to right. Find drawing number 1 and in column number 2 across the top of the page, locate wire number 2. Figure 16: Elementary Wiring Diagram Quantech...
FROM TRANSFORMER -1T =2-EEVC INPUT CONFIGURATION 0-10V J15-4 P15 TO MICROBOARD STEP-1 J15-8 STEP-2 STEP-3 POLARITY DIRECTION RESPONSE TIME PULSE PER SECOND 200pps VALVE OPERATION TO SYSTEM #2 EEV 24V+ 24V- FROM TRANSFORMER -1T LD27951 Figure 21: EEV Controller Elementary Diagram Quantech...
2L1C 2L2C 2L3C 1L1A 1L2A 1L3A -QSD -QSD 1L1C 1L2C 1L3C TRANSFORMER AND TERMINALS ARE FOUND ON POWER SIDE 1L1A 1L2A 1L3A OF DIVIDER PANEL 1L1B 1L2B 1L3B 1L1C 1L2C 1L3C 140C LD13234C Figure 23: Power Options Connection Diagram Quantech...
Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft; top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit. Figure 26: Four Fan Units Dimensions – 3040THE, 3050THE, 3055THE, 3060THE, 3079THE Quantech...
Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft; top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit. Figure 27: Four Fan Units Dimensions – 3070TSE, 3075TSE, 3085TSE Quantech...
Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0''; top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit. Figure 28: Four Fan Units Dimensions – 3070TZJ Quantech...
Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft; top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit. Figure 29: Five Fan Units Dimensions – 3090THE Quantech...
Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0''; top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit. Figure 30: Five Fan Units Dimensions – 3095TZJ Quantech...
Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft; top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit. Figure 31: Six Fan Units Dimensions – 3095TSE, 3100THE, 3110TSE Quantech...
Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft; top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit. Figure 32: Eight Fan Units Dimensions – 3120THE, 3125TSE, 3129THE, 3140TSE Quantech...
Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0''; top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit. Figure 33: Eight Fan Units Dimensions – 3140TZJ Quantech...
Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft; top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit. Figure 34: Ten Fan Units Dimensions – 3160TSE, 3150THE, 3170THE Quantech...
Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft; top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit. Figure 35: Twelve Fan Units Dimensions - 3205THE, 3225THE Quantech...
This informa- and location measurements for each isolator. tion will be available when the specific chiller/ option selection is made from the local Quantech sales office. Sample isolator location drawings Be aware, weights will change with each option along with possible isolator changes.
(2 m) (1.3 m) NOTES: 1. No obstructions allowed above the unit. 2. Only one adjacent wall may be higher than the unit. 3. Adjacent units should be 10 ft (3 m) apart. Figure 37: Unit Clearances – All Models Quantech...
Form QTC3-NM1 Section 5: Technical data Issue date: 12/19/2023 Isolator locations Four fan isolator locations - 3040THE, 3050THE, 3055THE, 3060THE, 3079THE LD18078 Four fan isolator locations - 3070TSE, 3075TSE, 3085TSE LD18079 All dimensions are inches unless otherwise specified. Quantech...
Page 109
Form QTC3-NM1 Section 5: Technical data Issue date: 12/19/2023 Five and six fan isolator locations - 3090THE, 3110TSE, 3095TSE, 3100THE LD18080 Eight fan isolator locations - 3125TSE, 3140TSE, 3129THE LD18081 All dimensions are inches unless otherwise specified. Quantech...
Page 110
Form QTC3-NM1 Section 5: Technical data Issue date: 12/19/2023 Ten fan isolator locations - 3160TSE, 3150THE, 3170THE LD18082 Twelve fan isolator locations - 3205THE, 3225THE VIEW LD21040 All dimensions are inches unless otherwise specified. Quantech...
Type b model p/n RATED CAPACITY (LB) DEFLECTION RATED (IN.) COLOR CODE 029-25334-008 (433997) 1350 1.320 DK. PURPLE 029-25334-009 (433998) 1800 1.020 DK. GREEN 029-25334-010 (433999) 2400 0.900 GRAY 029-25334-012 (434000) 2720 0.770 WHITE 029-25334-013 (434001) 3570 0.880 GRAY / RED Quantech...
Page 112
10. Installation is complete. 4. Bolt or anchor all isolators to supporting structure utilizing base slotted holes (“C”). 5. Place equipment on top of isolators making sure that mounting holes of the equipment line up with isolator positioning pin (“H”). LD13790 Quantech...
Page 114
13. Installation is complete. of (2) 5/8 UNC A325 grade 5 SAE bolts or weld ("G") ("E") ("A") ("A") ("E") GROMMET 1/4 - 3/8 GAP EQUIPMENT ("F") WASHER ("E") ("F") ("C") ("C") ("B") LD13763B Quantech...
Page 115
029-25335-001 (434002) CHARCOAL UP TO 825 UP TO 374 TYPE B MODEL P/N ISOLATOR COLOR WEIGHT RANGE (LB) WEIGHT RANGE (KG) 029-25335-002 (434004) BRICK RED 826 TO 1688 375 TO 766 029-25335-004 (434005) CHARCOAL 1689 TO 4000 767 TO 1814 Quantech...
Page 116
(“A”) be in- stalled on a level surface. Shim or grout as re- quired, leveling all isolator bases to the same elevation (1/32 in. maximum difference can be tolerated). TOP BOLT ("B") TOP WASHER ("C") ("B") ("A") SECTION D-D LD13762B Quantech...
Issue date: 12/19/2023 Section 6: Commissioning Commissioning of this unit should only coils with the full operating charge as given in Section be carried out by Quantech Authorized 5: Technical data. personnel. ALWAYS keep the water pump running when vacuuming the system, removing...
Page 118
To add oil to a circuit, complete the following steps: the system. Open the angle valve 1.5 turns. Close 1. Connect a Quantech hand oil pump (P/N 470- it after one pound is added. Wait another 15 min. 10654-000) to the 1/4 in. oil charging connection...
SYSTEM SWITCHES tures, the coolers should be drained or power should be key are in the OFF position. applied to the chiller. This will allow the cooler heater to protect the cooler from freezing down to –20°F. Be- Quantech...
There should be a straight run of at least 5 pipe diam- eters on either side of the flow switch. The flow switch should be connected to terminals 13 and 14 of XTBC1 on the panel. LD18420 Quantech...
Page 121
8. Change parameter 0-20 back to default value of option 1601 – “Reference [Unit]”. 9. Change parameter 0-22 back to default value of option 1610 – “Power [kW]”. 10. Put the VFD back into AUTO mode. LD18424 Quantech...
Analog input 1 offset 23.5 1302 Analog input 1 scaling 1850 2007 Min frequency limit 2008 Max frequency limit See motor nameplate (50 Hz, 60 Hz) 2102 Stop mode 2202 Accel time 30.0 2203 Decel time 30.0 2601 Energy optimizer Quantech...
5. Set l3 to 10, which is the sum of all dip switches 2. Set l1, the trip setting. in the up position. l1 = ln x (0.4 + the sum of the dip There are no requirements for adjusting the other switch settings) switches. LD29345 Figure 40: Circuit breaker panel Quantech...
1/8 to full SG Bottom of SG Bottom of SG 1/8 to full SG Bottom of SG Bottom of SG Bottom of SG Bottom of SG 1/8 to full SG Bottom of SG 1/8 to full SG Bottom of SG Quantech...
Page 125
... Note: Power must be applied 24 hours before start-up. Each 9. Check that all power is wired to the chiller and meets heater should draw approximately 0.5 A to 1 A. the following NEC and local codes. Quantech Quantech...
Page 126
5. Turn system 2 OFF and leave system 1 running. Refer to QTC3-ICOM6, Section 6: Operations, Unit External evaporator pump Keys for more information on system switches..Quantech hydro kit pump 6. Connect a manifold gauge to system 1 suction and Pump selection discharge service valves ..........
Page 127
15 min, between adjustments for the system and the thermal expansion valve to respond and stabilize. Ensure that superheat is set at a minimum of 10°F (5.56°C) with a single compressor running on each circuit. Quantech Quantech...
Page 128
Form QTC3-NM1 Section 6: Commissioning Issue date: 12/19/2023 This page is intentionally left blank. Quantech...
LD19046 Introduction IPU II and I/O boards The Quantech Control Center is a microprocessor based The IPU and I/O boards are assembled to function as control system designed to provide the entire control a single microprocessor controller. The IPU II board for the liquid chiller.
1 a second. Display Messages may show characters indicating “greater than” (>) or “less than” (<). These characters indicate the actual values are greater than or less than the limit values which are being displayed. Quantech...
OPTIONS is turned OFF. The system will not be al- The REMOTE CONTROLLED SHUTDOWN mes- lowed to run until the switch is turned back ON. sage indicates that either an ISN system or RCC has turned the unit OFF, not allowing it to run. Quantech...
Page 132
STATUS display mode. There- trol will not function unless the discharge transducer is fore, do not expect to see any other STATUS messages installed in the system. when in the MANUAL OVERRIDE mode. MANUAL Quantech...
Page 133
40 psig below the cutout. Discharge transducers must be installed for this function to operate. Quantech...
Page 134
1 H I G H M T R C U R R 90 minutes and the fault cannot be reset until the fault S Y S H I G H M T R C U R R condition is resolved. Quantech...
Page 135
On units with two pumps, duty and standby: This indi- trip voltage for 5 seconds. cates that both the manual motor starters protecting the pumps from short circuit or overload conditions have Quantech...
Page 136
The Motor Protector/High Pressure Cutout protects the System safety motor from overheating or the system from experienc- Discharge pressure cutout ing dangerously high discharge pressure. This fault condition is present when CR1 (SYS 1) or CR2 (SYS When the operating envelope is disabled, the discharge Quantech...
Page 137
Fault and inhibit codes and reset Table 14 on page 122 shows the fault and inhibit codes and how to reset them. There are three ways to reset the fault and inhibit. See on page 103 for more information. Quantech...
Low Discharge Superheat Auto Table 16: Legend Type Definition Automatically restarts on the first and second fault with a lockout on the third fault in 90 minutes Locks out on the first fault Auto Allows restart once meeting the required conditions Quantech...
A M B I E N T A I R T E M P 8 7 . 5 ° F This display shows the ambient air temperature. The minimum limit on the display is 0.4°F (-17.6°C). The maximum limit on the display is 131.2°F (55.1°C). Quantech...
Page 141
A detailed description of unit loading and unloading is perature rises above 45°F the heater is turned OFF. An covered under the topic of Capacity Control. under voltage condition will keep the heater OFF until full voltage is restored to the system. Quantech...
Page 142
LOAD LIM – Load limiting enabled using contact clo- sure. See Standard condenser fan control on page 175 for more information. PWM TEMP – EMS temperature reset *See Remote BAS/EMS temperature reset using a voltage or current signal on page 180. Quantech...
3MIN Current Feedback One Per System BIVALENT HEAT DELAY TIME 30 MIN REMOTE UNIT ID PROGRAMMED QUANTECH HYDRO KIT PUMPS 1(410a) * Block of information repeats for each system LD12585 PUMP TOTAL RUN HOURS XXXXX (410a) UNIT DATA Figure 44: Operation data RETURN LIQUID TEMP 58.2 DEGF...
Page 144
JOHNSCON CONTROLS INTERNATIONAL THU START=00:00AM STOP=00:00AM CORPORATION FRI START=00:00AM STOP=00:00AM MILLENNIUM LIQUID CHILLER SAT START=00:00AM STOP=00:00AM HOL START=00:00AM STOP=00:00AM SAFETY SHUTDOWN NUMBER 1 SHUTDOWN @ 3:56PM 29 SEP 07 SYS 1 HIGH DSCH PRESS SHUTDOWN SYS 2 NO FAULTS Quantech...
Page 145
X X X X X X X X X X Displays the type of Ambient Control; Standard or Low Ambient. L O C A L / R E M O T E M O D E X X X X X X X X X Quantech...
Page 146
A M B I E N T A I R T E M P Displays the System Suction Temp and Saturated Suc- X X X . X ° F tion Temp when an EEV is installed. Quantech...
Page 147
C. M X X. Z Z. Y Y S Y S A C T U A L A M P S I / O C. M X X. 1 8. Y Y = X X X . X A M P S Quantech...
The ↑ (UP) arrow key, and ↓ (DOWN) arrow key are also used for programming the control panel such as changing numerical or text values when programming cooling setpoints, setting the daily schedule, changing safety setpoints, chiller options, and setting the clock. Quantech...
After adjusting the setpoint, the ENTER/ADV key point display entry screen will appear. must be pressed to enter the data into memory. Notice that the RANGE was programmed for +/- X.X°F. This indicates the SETPOINT to be in the Quantech...
ISN control, remote reset option board, or remote PWM signal. These setpoints would only be To set the schedule, press the SCHEDULE/ADVANCE valid if the unit was operating in the REMOTE mode. DAY key. The display will immediately show the fol- lowing display. Quantech...
30°F (-1.1°C). * When using glycol, Leaving Chilled Liquid Setpoint must not be set below 10°F (-23.3°C). ** If the setpoint exceeds 55°F (12.8°C), contact the nearest Quantech Office for application guidelines. After SUN (Sunday) schedule appears on the display...
Typically, the cutout should be set to 87 psig (6.00 bar) form water cooling. F A N C O N T R O L P R E S S U R E X X X P S I G Quantech...
Page 153
OPER DATA key. The approximate C U T O U T = XXXX PSIG programmed value is calculated using the following A N T I - V A C D E L A Y T I M E formulas. S E C Quantech...
* The minimum discharge pressure allowed is 235 psig. The high limit for fan differential off pressure is reduced to prevent going below 235 psig based on where the fan control on pressure is programmed. LD07404c Figure 45: Setpoints Quick Reference List Quantech...
Evaporator pump control — — EXTERNAL, EXTERNAL KIT PUMPS 1 or KIT PUMPS 2 Evaporator pump total run hours (R-410A/ R-454B chiller or heatpump) 99999 — (1 Inc./Dec. per entry position) R-410A/R-454B Control Mode — — LEAVING or LEAVING RETURN Quantech...
Page 157
GRAM, ↓, ↑, ↑, ↓, ENTER in sequence. 3. To select the required option, use the ↑ and ↓ keys. See on page 103 and on page 103 for the mod- ified limits when the low temperature glycol is enabled. Quantech...
O F F English, Spanish, French, German, Italian, Portuguese, This turns systems 1 and 2 OFF. Hungarian, Polish, and Swedish can be programmed. Turning a system OFF with its system switch allows a pumpdown to be per- formed before shutdown. Quantech...
Page 159
ISN to control the following items: Re- mote Start/Stop, Cooling Setpoint, Load Limit, and History Buffer Request. If the unit receives no valid ISN transmission for 5 minutes, it will revert back to the locally programmed values. Quantech...
Page 160
This mode must be chosen. F A N C O N T R O L A M B I E N T & D S C H P R E S S Do not select this option on R-410A chillers. Quantech...
Page 161
A Flash Card is used to input the operating program cessor will store the change. into the chiller IPU. A Flash Card is used instead of an EPROM. Normally, a Flash Card update is not required and the message above will be displayed. Quantech...
Page 162
P U M P S After the update is completed, an automatic reboot will When Quantech HYDRO KIT PUMPS = 1, the con- occur. If an error occurred, the following message will trols will be closed to run the pumps whenever any one appear with the error code and no reboot will occur.
Page 163
Option 21: Flash card data logging The displays for this PUMP SELECTION option When the following message appears, data logging is should only appear if “QUANTECH HYDRO KIT disabled. PUMPS = 2” are selected under Option 19. D A T A L O G...
Page 164
Pressing the ENTER/ADV key will save the valve and wise the daily schedule will not function as required if move the cursor on to the next programmable variable. programmed. In addition, for ease of troubleshooting via the History printouts, the day, time, and date should be correct. Quantech...
(”Chiller” MUST be Selected Via No Jumper Installed (Viewable Only) Refrigerant Type R-410A (Programmed under Service Mode) Viewable Only) LD07405d Figure 46 provides a quick reference list for the Unit key setpoints. Figure 46: Unit Keys Options Programming Quick Reference List Quantech...
Go to the Johnson Controls Chillers Address for these points is 1537 + BV #. Knowledge Exchange website for the most up-to-date SC-EQ BAS point maps: https://docs.johnsoncontrols.com/chill- ers/. You can also contact your local Quantech office for a copy of the data map. Quantech...
4. Water Cooled Scroll units use the same firmware as Air Cooled Scroll units, ignoring Fan Control. The following table shows the real time error numbers that may be encountered during communication setup and a description of each. Quantech...
Page 170
Knowledge Exchange website for the control values. These values are found under feature 54 most up-to-date SC-EQ BAS point maps: in the E-Link Gateway. https://docs.johnsoncontrols.com/chill- ers/. You can also contact your local Quantech office for a copy of the data map. Quantech...
6. If demand requires, the lag system will cycle ON with the same timing sequences as the lead system after the lead system has run for five min- utes. See the section on Capacity Control for a detailed explanation of system and compressor staging. Quantech...
Upon energizing any compressor, the 60 sec- can be from plus or minus1.5°F to plus or minus 2.5°F ond Anti-Coincidence timer will be initiated to prevent (plus or minus 0.83°C to 1.39°C).leaving chilled liquid multiple compressors from turning ON. control. Quantech...
50°F, the setpoint high limit is set to 50°F and the dif- ference is added to the setpoint low limit. When a system runs for greater than 5 minutes, the set- point adjust sets back to 0. This occurs while the sys- tem is still running. Quantech...
Return chilled liquid system lead/lag and compressor sequencing Evaporator pump control and Quantech hydro kit pump control A Lead/Lag option may be selected to help equalize average run hours between systems with 2 refriger- The evaporator pump dry contacts (XTBC2 – Termi- ant systems.
385 psig with a operating mode to lock the switch electronically. differential of 125 psig. To unlock the flow switch, perform the same oper- ation again. The setting remains the same in case of power failure. Quantech...
20 seconds. ** When a fan stage is turned off (Programmed ON pressure minus the differential), the OFF pressure for the next stage is decreased 20 psig and ramped back to the programmed OFF pressure minus the differential. Quantech...
20 seconds. ** When a fan stage is turned off (Programmed ON pressure minus the differential), the OFF pressure for the next stage is decreased 20 psig and ramped back to the programmed OFF pressure minus the differential. Quantech...
The first stage of limiting is either 80%, 66% or 50%, ences a loss of power to the chiller electronics . System 1 alarm contacts are located at XTBC2 – Terminals 29 Quantech...
New Setpoint = 7.22°C + 6.67°C = 13.89°C * Max Reset Value is the “Max EMS-PWM Remote Temp. Reset” setpoint value described in Remote setpoint control on page 150 under “Cooling Setpoints”. Programmable values are from 2°F to 40°F (1.11°C to 11.11°C). Quantech...
REFRIGERANT TYPE (R-410A only) in this mode. Otherwise, turning the unit switch ON EXPANSION VALVE TYPE (Thermostatic Only) will take the panel out of Service Mode. REMOTE TEMP RESET OPTION = REMOTE INPUT SERVICE TIME = Quantech...
** The suction temp. sensor is on EEV units only. FEATURE SET The analog inputs will display the input connection, PUMP CONTROL SELECTION the temperature or pressure, and corresponding input SYS 1 HOURS voltage such as: SYS 2 HOURS SYS 1 STARTS Quantech...
J6-6 = +5 VDC regulated supply to sensor. J6-9 = VDC input signal microboard. See Table 31 on page 185 for voltage readings that correspond to specific outdoor tempera- tures. J6-3 = drain (shield connection = 0 VDC) return Quantech...
650 psig. The output will be linear from 0.5 VDC to 3.54 4.5 VDC over the 600 psig (41.25 barg) range. Follow- ing is the formula that can be used to verify the volt- age output of the transducer. All voltage reading are in reference to ground (unit case). Quantech...
The voltage applied to either of these J9-6 = +5 VDC regulated supply to transducer. terminals would be determined by field wiring. J9-11 = VDC input signal to the microboard. See the formula above for voltage readings that correspond to specific discharge pressures. Quantech...
Detailed explanation of the print function is tion, 25 ft (7.62 m) maximum length. given under Print key on page 143. 4. One 25 pin Cannon connector and shell. 5. Cannon P/N DB-25P connector, or equivalent. 6. Cannon P/N DB-C2-J9 shell. Quantech...
5. Defective IPU II & I/O Board or 5. Replace IPU II & I/O Board or the Display the Display Board. Board. Contact Quantech Service be- fore replacing circuit Boards! 1. No chilled liquid flow. 1. Check chilled liquid flow.
Page 194
3. Contactor/Overload failure. 3. Replace defective part. 4. Compressor failure. 4. Diagnose cause of failure and replace. 1. Fouled evaporator surface. 1. Contact the local Quantech service Low suction pressure will be representative. observed. 2. Improper flow through the 2. Reduce flow to within chiller design specs.
Important If system failure occurs due to improper maintenance Condenser round tube coils during the warranty period, Quantech will not be liable Ensure dirt does not accumulate on the condenser coil for costs incurred to return the system to satisfactory surfaces.
Page 196
• Do not use caustic or acidic cleaning solutions on 3. Apply a coil cleaning solution approved by Quan- tech. Quantech approves the use of RectorSeal coils. Only use cleaning solutions approved by brand GulfClean coil cleaner, or equivalent, Quantech.
Page 197
3. Apply a coil cleaning solution approved by Quan- the following section to touch-up the e-coat after tech. Quantech approves the use of RectorSeal cleaning. brand GulfClean coil cleaner, or equivalent, on...
Perform regular checks on the system to ensure that operating temperatures and pressures are within limi- tations, and that the operating controls are set within proper limits. See Section 8: Unit operation, Section 6: Commissioning, and Section 4: Installation. Quantech...
(°C), subtract 32° and multiply by 5/9 or 0.5556. Example: (45.0°F - 32°) x 0.5556 = 7.22°C To convert a temperature range (i.e., a range of 10°F) from Fahrenheit to Celsius, multiply by 5/9 or 0.5556. Example: 10.0°F range x 0.5556 = 5.6 °C range Quantech...
Page 203
Form QTC3-NM1 Section 10: Maintenance Issue date: 12/19/2023 This page is intentionally left blank. Quantech...