Semi-Hermetic Quantech Twin-Screw Compressors; Evaporator; Condenser; Refrigerant Circuit - Quantech QTC4 STYLE A Series Installation Operation & Maintenance

Air-cooled screw liquid chillers with variable speed drive, 150 - 500 tons, 525 - 1750 kw, 2 compressor, 60 hz
Hide thumbs Also See for QTC4 STYLE A Series:
Table of Contents

Advertisement

FORM QTC4-NM1
ISSUE DATE: 4/2/2018
SEMI-HERMETIC QUANTECH TWIN-SCREW
COMPRESSORS
Compressors are direct drive, semi-hermetic, rotary
twin-screw type, including: muffler, temperature actu-
ated 'off-cycle' heater, IP55 terminal board and preci-
sion machined cast iron housing.
Reliable
suction
gas
accessible hermetic compressor motor, full suction gas
flow through mesh screen filter, with inherent internal
thermal overload protection and external current over-
load on all three phases.
Continuous
function,
microprocessor
Variable Speed Drive (VSD) shall provide valve-less,
smooth capacity control from 100% down to 10% of
chiller capacity.
In addition, elimination of the slide valve and asso-
ciated unloading components has resulted in a 50%
reduction in compressor moving parts.

EVAPORATOR

The evaporator is a shell and tube, hybrid falling film
type heat exchanger. It contains a balance of flooded
and falling film technology to optimize efficiency, min-
imize refrigerant charge, and maintain reliable control.
A specifically designed distribution system provides
uniform refrigerant flow for optimum performance.

CONDENSER

The QTC4 introduces micro-channel coil to the
Quantech screw compressor chiller line. The micro-
channel maximizes condenser heat transfer, resulting
in a smaller footprint, and reduces refrigerant charge
by as much as 50%.
Each condenser coil is a single piece all aluminum
construction including headers, tubes and fins to avoid
galvanic corrosion due to dissimilar metals. Coils and
headers are brazed as one piece. Integral sub-cooling
is included. The design working pressure is 375 PSIG
(25.9 barg).
Multiple, standard low sound, high efficiency, TEAO
motor driven fans move air through the coils. They are
dynamically and statically balanced, direct drive with
corrosion-resistant glass fiber reinforced composite
blades molded into low-noise, full airfoil cross sec-
tions, providing vertical air discharge from extended
orifices for efficiency and low sound.
QUANTECH
cooled,
high
efficiency,
controlled,
SECTION 2 - PRODUCT DESCRIPTION
Fan motors are Totally Enclosed Air-Over (TEAO),
squirrel-cage type and current protected. The direct
drive motors feature double-sealed and permanently
lubricated ball bearings, cutting down on maintenance
cost over the life of the unit.

REFRIGERANT CIRCUIT

An independent refrigerant circuit is provided per
compressor. Each circuit uses copper refrigerant pipe
formed on computer controlled bending machines to
reduce the number of brazed joints resulting in a reli-
able and leak resistant system.
• Discharge lines are provided with a manual com-
pressor shutoff service valve (See Accessories
and Options on Page 19 for suction line service
valve).
• The external oil separators, with no moving parts
and designed for minimum oil carry-over, are
mounted in the discharge line of the compressor.
• Liquid line components include: high absorp-
tion removable core filter-drier, sight glasses with
moisture indicators, manual shut-off valve with
charging port, orifice and electronic expansion
valve.
• An economizer (flash) tank is located in each re-
frigerant circuit to increase the system efficiency.

ELECTRICAL

Quantech has years of experience designing Variable
Speed Drives (VSDs) specifically for chiller applica-
tions. The result is an extremely reliable air-cooled
chiller system that offers industry leading efficiency at
real world operating conditions, valve-less compres-
sor loading/unloading, excellent capacity control, high
power factor and soft start.
Incoming single point power is standard utilizing a
lockable circuit breaker, 115VAC control transformer,
VSD, fan contactors, ON/OFF unit switch, microcom-
puter keypad and display, Chiller Control and VSD
Logic boards, and relay boards.
Standard design includes IP55 rating, powder painted
steel cabinet with hinged, latched, and gasket sealed
outer doors equipped with wind struts for safer servic-
ing. The panel includes a control display access door so
that display and control features can be accessed with-
out opening main cabinet doors. All exposed power
wiring is routed through liquid-tight, UV-stabilized,
non-metallic conduit.
2
17

Advertisement

Table of Contents
loading

Table of Contents