Air-cooled inverter scroll chiller and heat pump (20 pages)
Summary of Contents for Quantech QWC3050T-200T
Page 1
WATER-COOLED LIQUID CHILLERS HERMETIC SCROLL Supersedes: QWC3-NM1 (1118) Form: QWC3-NM1 (1120) INSTALLATION, OPERATION, MAINTENANCE PART # 035-26707-000 QWC3050T-200T WATER-COOLED LIQUID CHILLERS STYLE A (60 HZ) 50 - 200 TONS 175KW THROUGH 700KW R410A Issue Date: Products are produced at a...
Page 2
All wiring must be in accordance with Quantech’s published specifications and must be performed only by a qualified electrician. Quantech will NOT be responsible for damage/problems resulting from improper con- nections to the controls or application of improper control signals.
Page 3
Any references to Sys 2 are applicable to QTC2015T-045T models. ASSOCIATED LITERATURE MANUAL DESCRIPTION FORM NUMBER Unit Replacement Parts QWC3--RP1 Unit Start-Up Checklist QWC3-CL1 All Products - Replacement Parts Electrical Connectors 50.20-RP1 All Products - Replacement Parts Fittings 50.20-RP2 QUANTECH...
Page 4
FORM QWC3-NM1 ISSUE DATE: 11/20/2020 THIS PAGE INTENTIONALLY LEFT BLANK. QUANTECH...
FORM QWC3-NM1 ISSUE DATE:11/20/2020 SECTION 1 – GENERAL CHILLER INFORMATION AND SAFETY INTRODUCTION • Only genuine Quantech approved spare parts, oils and refrigerants must be used. QWC3 chillers are manufactured to the highest design • All the scheduled maintenance operations detailed...
Electrical the unit. The unit must be grounded. No installation or main- tenance work should be attempted on the electrical equipment without first switching power OFF, isolat- ing and locking-off the power supply. Servicing and QUANTECH...
Two independent refrigerant circuits are provided on and fully charged with environmentally friendly refrig- each unit. Each circuit uses copper refrigerant pipe erant (R410A) and Quantech oil in each of the inde- formed on computer controlled bending machines to pendent refrigerant circuits.
(6) of Section VII, Division 1 of ASME Pressure Ves- • Forty character liquid crystal display, with de- sel Code. The condenser is equipped with relief valves scription available in five languages (English, and will hold the full refrigerant charge for pumpdown. French, German, Spanish or Italian). QUANTECH...
• Compressor starts and operating hours (each com- the unit supply voltage to 115V, 1-phase, 60Hz for pressor) the control system. • Run permissive status • Number of compressors running • Liquid solenoid valve status • Load and unload timer status • Water pump status QUANTECH...
This option will reduce the chiller MCA (minimum circuit ampac- Double Thick Insulation ity) and allow for reduced wire sizing to the unit. This Double thick (1-1/2") insulation provided on the evap- orator. (Factory-Mounted) QUANTECH...
Page 17
(Factory- Mounted) able, deflection may vary slightly by application. (Field- Mounted) Non Reversing Heat Pump Unit configured for optional operating mode controlled by leaving condenser water temperature. Temperature setpoint user adjust from 86°F to 122°F (30°C to 50°C), QUANTECH...
SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE:11/20/2020 UNIT COMPONENTS (CONT’D) LIQUID LINE SOLENOID EVAPORATOR VALVE WATER OUTLET LD12920 LIQUID STOP LIQUID LINE DRIER VALVE EVAPORATOR / INLET WATER FIGURE 5 - CONTROL / POWER PANEL COMPONENTS DUAL SYSTEM UNITS QUANTECH...
115T 46 = 460-3-60 130T 58 = 575-3-60 150T 170T REFRIGERANT = R-410a 200T QWC3 = QUANTECH CHILLER WATER COOLED SCROLL TABLE 1 - PRODUCT IDENTIFICATION NUMBER FEATURE FEATURE DESCRIPTION OPTION OPTION DESCRIPTION CONTRACT Contract Number Contract Number = {CONTRACT/NUM}...
Page 23
Leaving Condenser Water Temp = {CTEMP/NUM} CTEMP degrees (PIN 26 and 27) Special Quote No Sequence Kit PIN 28 PIN 28 Special Quote Leaving Evaporator Water Temp = {TEMP/NUM} Evaporator Water Temp degrees TEMP (PIN 29 and 30) Special LST requirements QUANTECH...
Page 24
Three Differential Pressure Switches/chiller EVAPFLOW Evap Flow Switch (PIN 41) One Flow Switch/chiller Two Flow Switches/chiller Three Flow Switches/chiller Special Quote ASME Pressure Vessel and Associated Codes VESSEL Vessel Codes (PIN 42) European “CE” Pressure Vessel Directive Special Quote QUANTECH...
Page 25
FORM Shipment Form (PIN 51) Special Quote No option PIN52 (PIN 52) Special Quote No Final Overspray Paint PAINT Overspray Paint (53) Final Overspray Paint Special Quote No Isolators 1" Deflection ISOL Isolators (PIN 54) Neoprene Seismic Special Quote QUANTECH...
The low pressure liquid refrigerant increased. High-pressure vapor is passed through the then returns to the evaporator. FIGURE 6 - REFRIGERANT FLOW DIAGRAM QUANTECH...
Sensor Pressure or Temperature 38.6 bar 36.3 bar 34.7 bar Service (Stop) Access Valve Refer to Pressure Switch Options Filter Drier (Removable Core) 27.6 bar Refer to Option Options Compressors Evaporator -YLLSV LD12938 FIGURE 7 - PROCESS AND INSTRUMENTATION DIAGRAM QUANTECH...
Page 28
FORM QWC3-NM1 ISSUE DATE: 11/20/2020 THIS PAGE INTENTIONALLY LEFT BLANK. QUANTECH...
Refer to and comply with procedures noted in the doc- Major damage must be reported immediately to your ument titled Long-Term Storage Requirements General local Quantech representative. (Form 50.20-NM1). MOVING THE UNIT Ensure that all openings, such as water connections, are securely capped.
The clearances recommended are nomi- ment must be commissioned and serviced nal for the safe operation and mainte- by an authorized Quantech service me- nance of the unit and power and control chanic or a qualified service person expe- panels. Local health and safety regula- rienced in chiller installation.
1” N.P.T. connection can be (13 mm) diameter holes in the base of the framework. When lower transmitted vibration levels are required obtained from Quantech as an option for optional anti-vibration isolators can be supplied loose the unit.
Page 33
Insulation should also be installed around if the unit is located in an unheated room where the heat exchanger nozzles. freezing could prevail. Water lines subjected to ambient temperatures below freezing may require heater cables or antifreeze (by others). QUANTECH...
FIGURE 9 - ANSI/AWWA C-606 - ADAPTER FLANGES Aerated, brackish or salt water is not recommended for use in the water system(s). Quantech recommends that a water treatment specialist is consulted to determine REFRIGERANT RELIEF VALVE PIPING...
In either case condenser cooling liquid flow and tempera- ture limits must also be observed. LD12941 FIGURE 11 - INLET TEMPERATURE CONTROL DIAGRAM LD12940 FIGURE 10 - DIRECT PRESSURE CONTROL DIAGRAM QUANTECH...
Quantech. The use invalidate the warranty. of a simple switch or timer from a remote point is per- mitted; but it must be connected to the Quantech unit No additional controls (relays, etc.) panel at points expressly indicated for that purpose.
This switch MUST remain in the OFF position until 5 – TECHNICAL DATA. the unit is commissioned by Quantech Authorized per- Connect the earth wire ground to the main protective sonnel. If the switch is set to the ON position before earth terminal in the common input section.
18 to 24 hours prior to restarting a com- a cutout of 532 PSIG (36.7 barg). These cutouts con- pressor. This will assured that liquid slugging and oil form to relevant requirements of Pressure Equipment dilution does not damage the compressors on start. Directive PD 97/23/EC. QUANTECH...
NO can result in damage to the evaporator LETHAL VOLTAGES are present inside and unit as a result of the chilled liquid the panel AFTER disconnecting power, freezing. PRIOR to working on equipment. FIGURE 16 - CONTROL WIRING QUANTECH...
40 (4.4) 115 (46) NOTES: 1. For leaving brine temperature below 40˚ (4.4˚C), contact your local Quantech Sales Representative for application requirements. 2. For leaving water temperature above 50˚ (10˚C), contact your local Quantech Sales Representative for application requirements. QUANTECH...
Special care should be taken when mul- 200-3-60 tiple chillers are fed by a single pump. 208-3-60 230-3-60 380-3-60 Voltage Limitations 460-3-60 575-3-60 The following voltage limitations are absolute and operation beyond these limitations may cause serious damage to the compressor. QUANTECH...
X ft. (mm x m) (279 x 2.4) (279 x 2.4) (279 x 2.4) (279 x 2.4) (330 x 2.4) (356 x 2.4) (356 x 2.4) (406 x 2.4) (381 x 3.0) (43 X 3) (43 X 3) Water Nozzle Connection Size, in. QUANTECH...
Page 47
17” X 10’ 17” X 10’ in. X ft. (mm x m) (406 x 2.4) (381 x 3) (406 x 2.4) (432 x 3) (432 x 3) (330 x 2.4) (406 x 2.4) (406 x 2.4) Water Nozzle Connection Size, in. QUANTECH...
To prevent serious injury or death, can result in damage to the evaporator the technician should verify that NO and unit as a result of the chilled liquid LETHAL VOLTAGES are present inside freezing. the panel AFTER disconnecting power, PRIOR to working on equipment. QUANTECH...
FORM QWC3-NM1 SECTION 5 – TECHNICAL DATA ISSUE DATE:11/20/2020 DUAL-POINT SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER LD17112 FIGURE 21 - DUAL POINT POWER SUPPLY CONNECTION – STANDARD UNIT QUANTECH...
AFTER disconnecting power, of the chilled liquid freezing. PRIOR to working on equipment. TABLE 8 - VOLTAGE RANGE (LIMITATIONS) VOLTAGE RANGE VOLTAGE CODE UNIT POWER MINIMUM MAXIMUM 200-3-60 230-3-60 380/415-3-60 460-3-60 380/415-3-50 575-3-60 QUANTECH...
9. The supplied disconnect is a “Disconnecting Means” as defined in the N.E.C. 100, and is intended for isolating the unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device. 10. Field Wiring by others which complies to the National Electrical Code & Local Codes. 11. Voltage Utilization Range QUANTECH...
(2) # 4 - 3/0 AWG Instructions: 1) Start in correct power option table (switch, breaker, terminal block) 2) Match engineering guide value for amperage 3) Match engineering guide value for wire range 4) Note corresponding ground wire range QUANTECH...
Page 65
FORM QWC3-NM1 SECTION 5 – TECHNICAL DATA ISSUE DATE:11/20/2020 THIS PAGE INTENTIONALLY LEFT BLANK. QUANTECH...
QWC3 050T, 060T, 070T, 080T, 090T, 100T, 115T and 130T STANDARD EFFICIENCY UNITS QWC3 060T, 070T, 080T, 090T, and 115T HIGH EFFICIENCY UNITS 035-21481-102 REV. B FIGURE 24 - POWER CIRCUIT, 4 COMPRESSOR WITH NON FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER QUANTECH...
ELEMENTARY WIRING DIAGRAM QWC3 050T, 060T, 070T, 080T, 090T, 100T, 115T and 130T STANDARD EFFICIENCY UNITS QWC3 060T, 070T, 080T, 090T, and 115T HIGH EFFICIENCY UNITS 035-21481-302 REV - FIGURE 25 - POWER CIRCUIT, 4 COMPRESSOR WITH CIRCUIT BREAKER QUANTECH...
QWC3095T, 130T and 150T HIGH EFFICIENCY UNITS 035-21499-102 REV D FOR 5 & 6 COMPRESSOR UNITS FOR 6 COMPRESSOR UNITS ONLY FOR 5 & 6 COMPRESSOR UNITS FOR 6 COMPRESSOR UNITS ONLY LD26948 FIGURE 26 - POWER CIRCUIT, 5 AND 6 COMPRESSOR QUANTECH...
FORM QWC3-NM1 SECTION 5 – TECHNICAL DATA ISSUE DATE:11/20/2020 ELEMENTARY WIRING DIAGRAM QWC3100T, 115T, 170T and 200T STANDARD EFFICIENCY UNITS QWC3095T, 130T and 150T HIGH EFFICIENCY UNITS 035-21499-302 REV - FIGURE 27 - POWER CIRCUIT, 6 COMPRESSOR QUANTECH...
FORM QWC3-NM1 SECTION 5 – TECHNICAL DATA ISSUE DATE: 11/20/2020 CONNECTION WIRING DIAGRAM QWC3100T, 115T, 150T, 170T and 200T STANDARD EFFICIENCY UNITS QWC3095T, 130T and 150T HIGH EFFICIENCY UNITS FIGURE 30 - CONNECTION WIRING DIAGRAM, 5 AND 6 COMPRESSOR QUANTECH...
Page 79
FORM QWC3-NM1 SECTION 5 – TECHNICAL DATA ISSUE DATE:11/20/2020 CONNECTION WIRING DIAGRAM (CONT’D) FIGURE 30 - CONNECTION WIRING DIAGRAM, 5 AND 6 COMPRESSOR (CONT’D) QUANTECH...
SECTION 5 – TECHNICAL DATA ISSUE DATE: 11/20/2020 CONNECTION WIRING DIAGRAM QWC3100T, 115T, 170T and 200T STANDARD EFFICIENCY UNITS QWC3095T, 130T and 150T HIGH EFFICIENCY UNITS 035-21499-104 REV E 6M/6OL ON 6 COMPR. LD26945a FIGURE 31 - CONNECTION WIRING DIAGRAM, 6 COMPRESSOR QUANTECH...
Page 81
CONNECTION WIRING DIAGRAM (CONT’D) Single HPCO - Standard for all panel (50Hz and 60Hz). . y l For 4 and 5 compressor models. Jumpers are included in panel assembly. . s l LD26945b FIGURE 31 - CONNECTION WIRING DIAGRAM, 6 COMPRESSOR (CONT’D) QUANTECH...
5. Contacts are rated at 115V, 100VA, resistive load only, and must be suppressed at load by user. 6. Optional current readout. 5V = 200A. 7. 1MP thru 6MP are contained in their respective compressor junction boxes. LD26944 FIGURE 33 - ELEMENTARY WIRING DIAGRAM DETAILS, 5 AND 6 COMPRESSOR QUANTECH...
Page 85
FORM QWC3-NM1 SECTION 5 – TECHNICAL DATA ISSUE DATE:11/20/2020 ELEMENTARY WIRING DIAGRAM DETAILS (CONT’D) 035-21499-103 REV. F LD26944 FIGURE 33 - ELEMENTARY WIRING DIAGRAM DETAILS, 5 AND 6 COMPRESSOR (CONT’D) QUANTECH...
J15-4 P15 TO MICROBOARD STEP-1 J15-8 STEP-2 STEP-3 POLARITY DIRECTION RESPONSE TIME PULSE PER SECOND 200pps VALVE OPERATION TO SYSTEM #2 EEV 24V+ 24V- FROM TRANSFORMER -1T FIGURE 34 - ELEMENTARY WIRING DIAGRAM, EEV CONTROLLER, 4 AND 6 COMPRESSOR QUANTECH...
(1270.0) (1270.0) (1270.0) (1270.0) (1270.0) (1270.0) (1270.0) (1270.0) (1270.0) (1270.0) (1270.0) H* - for 200/230 volt units, which require a larger electrical enclosure H** - for multiple point circuit breaker units, 200/230 volt, which require a larger electrical enclosure QUANTECH...
Page 88
FORM QWC3-NM1 SECTION 5 – TECHNICAL DATA ISSUE DATE: 11/20/2020 UNIT DIMENSIONS - FOUR COMPRESSOR (CONT’D) HIGH SIDE RELIEF VALVE LOCATIONS LOW SIDE RELIEF VALVE LOCATION QUANTECH...
37 21/32 (956.5) (956.5) (956.5) (888.2) (956.5) (1270) (1270) (1270) (1270) (1270) H* - for 200/230 volt units, which require a larger electrical enclosure H** - for multiple point circuit breaker units, 200/230 volt, which require a larger electrical enclosure QUANTECH...
Page 90
FORM QWC3-NM1 SECTION 5 – TECHNICAL DATA ISSUE DATE: 11/20/2020 UNIT DIMENSIONS - FIVE AND SIX COMPRESSOR QUANTECH...
Page 91
080T RD-4 Brick Red CP-2D-1800 Dark Green Pink/Gray 090T RD-4 Charcoal C2P-1D-2400 Gray Pink/Gray 095T RD-4 Charcoal C2P-1D-2400 Gray Pink/Gray 115T RD-4 Brick Red C2P-1D-2400 Gray Pink/Gray 130T RD-4 Charcoal C2P-1D-2720 White Pink/Gray 150T RD-4 Charcoal C2P-1D-3570 Gray/Red Pink/Gray/Orange QUANTECH...
Page 92
7-3/4 6-1/2 4-3/4 5-5/8 10-1/2 9-1/4 7-3/4 9/16 RATED CAPACITY (FOR UNITS WITH ALL LOAD POINTS LESS THAN MODEL COLOR QUANTECH P/N 1785 LBS (810 KG) NUMBER CODE (LBS.) (KG) CP-1D-510 BLACK Up thru 434 Up thru 197 029-25334-002 CP-1D-900...
Page 93
1/4" clearance is achieved between the lower tolerated). housing and upper housing. (See drawing below). 4. Bolt or anchor all isolators to supporting structure 9. Fine adjust isolators to level equipment. utilizing base slotted holes (“C”). 10. Installation is complete. QUANTECH...
Page 94
2.75 5.00 0.56 0.38 1/2-13 UNC X 1 3.00 MODEL NUMBER ISOL. COLOR WEIGHT RANGE (LBS) WEIGHT RANGE (KGS) QUANTECH P/N RD-3-CHARCOAL-WR CHARCOAL Up thru 825 UP TO 374 029-25335-001 RD-4-BRICK RED-WR BRICK RED 826 thru 1688 375 - 766...
Page 95
(“A”) be in- stalled on a level surface. Shim or grout as re- quired, leveling all isolator bases to the same elevation (1/32-inch maximum difference can be tolerated). TOP BOLT ("B") TOP WASHER ("C") ("B") ("A") SECTION D-D LD13762B QUANTECH...
Page 96
3. Equipment must be bolted or welded to the top plate to meet allowable seismic ratings. MODEL Y2RSI-2D SEISMICALLY RESTRAINED VIBRATION ISOLATOR FOR 2” DEFLECTION MODEL NUMBER ISOL. COLOR WEIGHT RANGE (LBS) WEIGHT RANGE (KGS) QUANTECH P/N Y2RSI-2D-460 GREEN Up thru 391 UP TO 177 029-25336-006...
Page 97
3" on center for a minimum total weld of 10". (All sides of equipment or bracket resting on top plate (“A”) must be welded). ("G") ("E") ("A") ("A") ("E") GROMMET 1/4 - 3/8 GAP EQUIPMENT ("F") WASHER ("E") ("F") ("C") ("C") ("B") LD13763B QUANTECH...
Page 100
Yellow w/ Red 1786 to 2028 lbs 910 to 920 kg CIP-C- Yellow w/ Green 2028 to 2254 lbs 920 to 1022 kg CIP-C- Red w/ Red 2254 to 2936 lbs 1022 to 1332 kg CIP-C- Red w/ Green QUANTECH...
Page 101
To use the isolator as blocking for the equipment, insert a 10. Installation is now complete. 10mm (1/4") shim between the upper load plate and vertical uprights. Lower the equipment on the blocking or shimmed isolators. QUANTECH...
Page 102
Weight Range (lbs) Weight Range (kg) Model Number Color Up to 751 lbs Up to 341 kg ND-C Yellow 751 to 1651 lbs 341 to 749 kg ND-D Yellow 1651 to 3226 lbs 749 to 1463 kg ND-DS Yellow QUANTECH...
Page 103
Pad can be removed if Enclosed Neoprene Restraining mounts are welded Steel Acoustical into position. Housing ENGLISH SIZE 8 1/2 1 3/8 12 1/4 5 1/4 3 1/ 2 2-C2 5/8 “ (215.9) (9.5) (15.9) (34.9) (355.6) (311.2) (133.4) (88.9) QUANTECH...
Page 104
MBD -Max 1/8" Bolt Diameter LOWER Rubber RESTRAINING Snubbing BOLTS Collar 1/4" Adjustment Bolt Non-Skid Neoprene Pad- Internal Lower Pad can be removed if Enclosed Neoprene Restraining SHIPPED & INSTALLED AFTER ADJUSTMENT mounts are welded Steel Acoustical into position. Housing QUANTECH...
FORM QWC3-NM1 ISSUE DATE:11/20/2020 SECTION 6 – COMMISSIONING Commissioning of this unit should only Compressor Oil be carried out by Quantech authorized To add oil to a circuit – connect a hand oil pump (Part personnel. No. 470-10654-000) to the 1/4” oil charging connec- tion on the compressors with a length of clean hose or copper line.
Set numbers 4 to 8 in accordance with the table shown in Figure 35 on page 106. For YLAA, YCWL and QWC3 chillers, DIP switch number 6 must be set to ON for a quicker EEV response. QUANTECH...
The inlet should be at the refrigerant piping connection end of the cooler. Purge air from the top of the cooler using the plugged air vent mounted on the top of the cooler body. QUANTECH...
Page 108
2 of CTB2. The voltage should be 120VAC +/- 10%..Power must be applied 24 hours prior to start-up Each heater should draw approximately 0.5-1A. 7. Check the control panel to ensure it is free of for- eign material (wires, metal chips, etc.)..... JOHNSON CONTROLS QUANTECH...
Page 109
Low Amb. Temp. Cutout Leaving Liquid Temp. Cutout Anti-Recycle Time Fan Control ON Pressure Fan Differential OFF Pressure Total # of Compressors * Number of Fans/System * Unit/Sys Voltage Unit ID * Not on All Models ** Viewable Only QUANTECH...
“lead” sys- will be allowed to run until the suction pressure tem. A new lead/lag assignment is made whenever falls below the suction pressure cutout or for 180 all systems shut down. seconds, whichever comes first. QUANTECH...
Page 112
FORM QWC3-NM1 SECTION 6 – COMMISSIONING ISSUE DATE: 11/20/2020 THIS PAGE INTENTIONALLY LEFT BLANK. QUANTECH...
INTRODUCTION IPU II and I/O Boards The IPU and I/O boards are assembled to function as a The Quantech MicroComputer Control Center is a mi- single microprocessor controller requiring no addition- croprocessor based control system designed to provide al hardware. The IPU II board contains a coldfire mi- the entire control for the liquid chiller.
Page 114
The system have 4, 5, or 6 compressors. parameters can be scrolled with the use of the ↑ (UP) and ↓ (DOWN) arrow keys. The display will update all information at a rate of about 1 a second. QUANTECH...
S W I T C H O F F not allow the unit to run. SYS SWITCH OFF tells that the system switch under OPTIONS is turned OFF. The system will not be al- lowed to run until the switch is turned back ON. QUANTECH...
Page 116
Therefore, it is important to keep in mind that this con- sages, etc. when in the STATUS display mode. There- trol will not function unless the discharge transducer is fore, do not expect to see any other STATUS messages installed in the system. QUANTECH...
Page 117
30VDC signal is restored to the input. allowed to restart when the discharge pressure falls 40 PSIG below the cutout. Discharge transducers must be installed for this function to operate. QUANTECH...
Page 118
90 minutes, ture (water or glycol) drops below the cutout point, the indicating the system is locked out and will not chiller will shutdown. Restart can occur when chilled restart. liquid temperature rises 2 °F above the cutout. QUANTECH...
Page 119
They are unit warn- This indicates the condensing unit jumper is installed ings and will not auto-restart. Operator intervention is on J11-12. This jumper must be removed to operate the required to allow a restart of the chiller. chiller. QUANTECH...
(Unit Warning Message) System X Comps Run System X AR Timer High Motor Current System X AC Timer System X Disch Limiting System X Suction Limiting System X Percentage Load Limiting Manual Overide Status System X Pumping Down (on shutdown) QUANTECH...
T E M P 8 7 . 5 ° F This display shows the ambient air temperature. The minimum limit on the display is 0.4 °F (-17.6 °C). The maximum limit on the display is 131.2 °F (55.1 °C). QUANTECH...
Page 122
Whether the systems loads or unloads is determined by how far the actual liquid temperature is from setpoint. A detailed description of unit loading and unloading is covered under the topic of Capacity Control. QUANTECH...
Page 123
The fourth message indicates the stage of condenser tact closure. fan operation that is active. This message does not ap- ply to QWC3 chillers and is displayed as a result of the • PWM TEMP – EMS temperature reset use of software common to QWC chillers. QUANTECH...
Current Feedback One Per Unit *System X Compressors Status *System X Run Time *Sys X LLSV & HGSV Status *System X Condenser Fan Stage (This message is not applicable to a QWC3 chiller.) Current Feedback One Per System LD22072 QUANTECH...
Page 125
DEFROST TERMINATION TIME 3MIN WED START=00:00AM STOP=00:00AM BIVALENT HEAT DELAY TIME 30 MIN THU START=00:00AM STOP=00:00AM REMOTE UNIT ID PROGRAMMED FRI START=00:00AM STOP=00:00AM QUANTECH HYDRO KIT PUMPS 1 (410a) SAT START=00:00AM STOP=00:00AM PUMP TOTAL RUN HOURS XXXXX (410a) HOL START=00:00AM STOP=00:00AM QUANTECH...
Page 126
A M B I E N T C O N T R O L follows. X X X X X X X X X X QUANTECH INTERNATIONAL CORPORATION Displays the type of Ambient Control; Standard or MILLENNIUM LIQUID CHILLER Low Ambient.
Page 127
Displays the Ambient Temp. at the time of the fault. Displays the Leaving Liquid Temp. Cutout pro- L E A D S Y S T E M grammed. S Y S T E M N U M B E R QUANTECH...
Page 128
C O N T R O L C. M X X. Z Z. Y Y S A T S U C T X X X . X ° F I / O C. M X X. 1 8. Y Y QUANTECH...
The ↑ (UP) arrow key, and ↓ (DOWN) arrow key are also used for programming the control panel such as changing numerical or text values when programming cooling setpoints, setting the daily schedule, changing safety setpoints, chiller options, and setting the clock. QUANTECH...
Notice that the RANGE was programmed for +/- X.X° F. This indicates the SETPOINT to be in the center of the control range. If the control mode has been pro- grammed for RETURN LIQUID control, the message below would be displayed in place of the previous message. QUANTECH...
Page 131
The following messages illustrate both leaving chilled M O N S T A R T 0 0 : 0 0 liquid control and return chilled liquid control respec- S T O P 0 0 : 0 0 tively. QUANTECH...
* When using glycol, Leaving Chilled Liquid Setpoint should not be set below 20°F (-6.7°C). ** Do not exceed 55°F (12.8°C) setpoint before contacting the nearest Quantech Sales Representative for application guidelines. The line under the 0 is the cursor. If the value is wrong,...
Page 133
Does not apply to QWC3. F A N D I F F E R E N T I A L O F F P R E S S U R E X X X P S I G Does not apply to QWC3. QUANTECH...
Page 134
V O L T S 225A 225A = X . X V O L T S The programmed value will be 2.8V. A similar calcula- tion and programming will be necessary for the other system in a 2-system chiller. QUANTECH...
REMOTE UNIT ID — * The minimum discharge pressure allowed is 235 PSIG. The Fan Differential Off Pressure High Limit will be lowered (reduced) to prevent going below 235 PSIG based on where the fan control ON Pressure is programmed. QUANTECH...
Provides a quick reference of the setpoints list for the Setpoints keys. Timer Fan Control On-Pressure (Not applicable to a QWC3) Fan Differential Off-Pressure (Not applicable to a QWC3) Total Numbers Compressors Number of Fans Per System SYS / Unit Trip Volts Option Remote Unit ID LD07404c QUANTECH...
English, Spanish, French, German, Italian, Portuguese, Hungarian, Polish, and Swedish can be programmed. This turns system 2 OFF S Y S S W I T C H O F F S Y S S W I T C H This turns system 1 OFF QUANTECH...
Page 138
BAS to control the following items: Re- mote Start/Stop, Cooling Setpoint, Load Limit, and History Buffer Request. If the unit receives no valid BAS transmission for 5 minutes, it will revert back to the locally programmed values. QUANTECH...
Page 139
CONDENSING UNIT modes. C U R R E N T F E E D B A C K O N E P E R U N I T QUANTECH...
Page 140
U P D A T E E R R O R XXXXX If the update resulted in an error, the original program will still be active. When an error occurs, assure the correct Flash Card was utilized. Incorrect chiller soft- QUANTECH...
Page 141
30 seconds to prevent pump overheating. When programmed for hot gas bypass type System 2, the unit will operate system 2 hot gas bypass if system 2 is the lead system. QUANTECH...
Page 142
E N A B L E D When the following option is selected, the discharge temperature sensors are disabled. D S C H T E M P S E N S O R S D I S A B L E D QUANTECH...
(”Chiller” MUST be Selected Via No Jumper Installed (Viewable Only)) Refrigerant Type R-410A (Programmed under Service Mode) Viewable Only) LD22073 Provides a quick reference list for the Unit key setpoints. FIGURE 36 - UNIT KEYS OPTIONS PROGRAMMING QUICK REFERENCE LIST QUANTECH...
Page 144
FORM QWC3-NM1 ISSUE DATE: 11/20/2020 THIS PAGE INTENTIONALLY LEFT BLANK. QUANTECH...
In water cooling mode on R-410A chillers, the mini- This control is only applicable if optional discharge mum low limit of the control range will be 40.0ºF. For pressure transducers are installed. leaving chilled liquid temperature setpoint and control QUANTECH...
50 number will always be the next compressor to start. °F, the setpoint high limit will be set to 50 °F, and the difference will be added to the setpoint low limit. QUANTECH...
Liquid Control the Hot Gas Bypass solenoid is energized only when the lead compressor is running and the LWT less than SP, the Hot Gas Bypass solenoid is turned OFF when the LWT more than SP plus CR/2. 2. Step 3 is skipped when loading occurs. 3. Step 4 is skipped when unloading occurs. QUANTECH...
Table 17 on page 150 shows the load limiting permit- key. If a dual pump option is installed, the active pump ted for the various number of compressors. Only Stage is selected by the selector switch. 1 is available utilizing a dry contact. QUANTECH...
°reset = (Contact Closure - 1) x (*Max. Reset Value) until power is reapplied and no fault conditions exist. Example: Local Chilled Liquid Setpoint = 45°F (7.22°C) *Max Reset Value = 10°F (5.56°C) Contact Closure Time = 6 Seconds. QUANTECH...
L L S V S T A T U S ENTER/ADV key is pressed: T B 10 - 3 O F F SYS 1 COMP 1 STATUS TB7-2 IS: SYS 1 LLSV STATUS TB7-3 IS: SYS 1 COMP 2 STATUS TB7-4 IS: QUANTECH...
7 – pin 10 (J7-10) on microprocessor will display the first programmable the I/O board. It indicates that the voltage is 2.1VDC value under the PROGRAM key. which corresponds to 81 PSIG (5.6 bars) suction pres- sure. QUANTECH...
Any time a switch or contact is closed, 30VDC would be applied to that par- ticular digital input. Any time a switch or contact is open, 0VDC would be applied to that particular digital input. QUANTECH...
100 to 240VAC power source. Connect the printers to the control center microboard Cancel printing by selecting the CANCEL PRINTING as follows. Only one printer can be connected at a time. option. CHOOSE PRINT REPORT will display when the PRINT key is pressed. QUANTECH...
History Buffer 1 History Buffer 2 History Buffer 3 History Buffer 4 History Buffer 5 History Buffer 6 History Buffer 7 History Buffer 8 History Buffer 9 History Buffer 10 Cancel Printing Press the key to initiate the printout. QUANTECH...
5. Defective IPU II & I/O board or 5. Replace IPU II & IO board or the Display board. Display Board. Contact Quantech Sales Representative before replacing circuit boards. 1. No chilled liquid flow. 1. Check chilled liquid flow.
Page 164
2. Compare the display with a sensor. thermometer. Should be within +/- 2 COMPRESSOR(S) WON’T START degrees. See the Service section for RWT/LWT temp./voltage table. 3. Contactor/Overload failure. 3. Replace defective part. 4. Compressor failure. 4. Diagnose cause of failure and replace. QUANTECH...
Page 165
ISSUE DATE:11/20/2020 TABLE 26 - TROUBLESHOOTING (CONT’D) PROBLEM CAUSE SOLUTION 1. Fouled evaporator surface Low 1. Contact the local Quantech Sales suction pressure will be observed. Representative. 2. Improper flow through the 2. Reduce flow to within chiller design evaporator.
Page 166
FORM QWC3-NM1 ISSUE DATE: 11/20/2020 THIS PAGE INTENTIONALLY LEFT BLANK. QUANTECH...
If system failure occurs due to improper maintenance during the warranty period, Quantech will not be liable for costs incurred to return the system to satisfactory OPERATING PARAMETERS operation. The following is intended only as a guide and covers only the chiller unit components.
Number is added to de modifier address, set as required by network. Unit operating software version 02 (C.MMC.13.02, C.MMC.14.02, Or C.MMC.16.02) Or higher required for MODBUS protocol functionality. Unit operating software version 04 (C.MMC.13.04, C.MMC.14.04, Or C.MMC.16.04) Or higher required for N2 protocol functionality. QUANTECH...
ALL OK and Modbus registers. DATUM TYPE OK TEST FAILED The latest data map information is listed ENGLISH TEXT TOO LONG on the Quantech website. FLOATING POINT EXCEPTION GET PACKET FAILED GET TYPE FAILED INVALID UNIT CONVERSION INVALID HARDWARE SELECTION...
FORM QWC3-NM1 SECTION 10 – MAINTENANCE ISSUE DATE:11/20/2020 TABLE 29 - BACNET AND MODBUS COMMUNICATIONS DATA MAP QUANTECH...
Page 172
FORM QWC3-NM1 SECTION 10 – MAINTENANCE ISSUE DATE: 11/20/2020 TABLE 29 - BACNET AND MODBUS COMMUNICATIONS DATA MAP (CONT’D) QUANTECH...
Page 173
FORM QWC3-NM1 SECTION 10 – MAINTENANCE ISSUE DATE:11/20/2020 TABLE 29 - BACNET AND MODBUS COMMUNICATIONS DATA MAP (CONT’D) QUANTECH...
Page 174
FORM QWC3-NM1 SECTION 10 – MAINTENANCE ISSUE DATE: 11/20/2020 TABLE 29 - BACNET AND MODBUS COMMUNICATIONS DATA MAP (CONT’D) QUANTECH...
Page 175
Table 30 on page 176 The latest point map information is listed “Yorktalk 2 Communications Data Map” lists the con- on the Quantech website. trol parameters. These values are found under feature 54 in the MicroGateway or E-Link.
(°C), subtract 32° and multiply by 5/9 or 0.5556. Example: (45.0°F - 32°) x 0.5556 = 7.22°C To convert a temperature range (i.e., a range of 10°F) from Fahrenheit to Celsius, multiply by 5/9 or 0.5556. Example: 10.0°F range x 0.5556 = 5.6 °C range QUANTECH...
Page 185