C70 Connection Manual

4.3 Connecting the Emergency Stop Signal

4.3 Connecting the Emergency Stop Signal
Connect the emergency stop signal to the connector EMG.
An external power supply is required, because Q173NCCPU module does not have 24VDC output for the
emergency stop signal.
Q 1 7 3 N C C P U
E M G
C a b l e H 1 0 0
Power supply
Q173NCCPU
+24VDC
10k
0V
Related items: Cable drawing: "Cable : H100 Cable"