a. Once the initial Ethernet connection is complete, access the web interface using a supported
browser and one of the following URLs:
http://ipaddress
- or-
https://ipaddress
(where ipaddress is the IP address of the management module).
NOTE: Supported browsers are:
•
Google Chrome, version 47 or later
•
Microsoft Internet Explorer, version 11 or later
•
Mozilla Firefox, version 42 or later
The default login to the web interface is:
•
Username: admin
•
Password: admin
b. To access HPE Adaptive Rack Cooling System settings, select the configuration tab on the right
side of the screen. The admin password can be changed using the button on upper right side of
webpage. A few of the pertinent menu options for initial setup are:
•
TCP/IP settings allow selection of DHCP or setup of static IP address.
•
The HTTP menu enables or disables the web interface and HTTP/HTTPS selection.
•
Console settings allow disabling or enabling of SSH and Telnet console access.
•
The Users menu under Security allows the admin to change user access levels and passwords.
2. If the HPE Adaptive Rack Cooling System Ethernet interface is not enabled or the network port cannot
be accessed, access the HPE Adaptive Rack Cooling System serially through the mini-USB port on
the front of the CMC to set up the Ethernet port for web access. The CMC contains an internal serial to
USB adapter. To communicate to the unit, use the following settings with a serial console program.
•
Bits per Second: 9600 (needs verification)
•
Data bits: 8
•
Parity: none
•
Stop bits: 1
•
Flow control: none
•
Username (default): admin
•
Password (default): admin
Once logged in, you can enable the port and configure the IP information. Use the web interface to
complete further detailed setup.
Installation
35