Connect Port 1 (DP1—left port) to the rack on the left side of the HPE Adaptive Rack Cooling
System.
Connect Port 2 (DP2—right port) to the rack on the right side of the HPE Adaptive Rack Cooling
System.
4. Secure the tubing between the port on the HPE Adaptive Rack Cooling System and the final
connection in the IT rack.
5. Mount the rear HPE Adaptive Rack Cooling System pressure pickup tube with the hose barb facing
right.
6. On the rear of the HPE Adaptive Rack Cooling System, join the two reference ports with a section of
the tubing and a Y-connector.
7. Connect the HPE Adaptive Rack Cooling System reference ports to the pressure pickup tube.
Installation
33