8. Install side panels at the end of each row of racks. For more information on installing side panel
blanks, see Installing the side panel blanks on the IT racks.

Configuring the unit

The HPE Adaptive Rack Cooling System design allows monitoring and management through an Ethernet
network interface. Configure basic configuration and operational set points on the front panel display.
Configure basic and advanced parameters remotely using a web user interface. When an HPE Adaptive
Rack Cooling System is first installed, you must configure the network on the unit. The following steps
detail how to set up the HPE Adaptive Rack Cooling System on the facility network, defaulting to DHCP
or setting up a static IP address and how to access the web user interface.
Ethernet setup:
Access and change the HPE Adaptive Rack Cooling System Ethernet settings using any of the following
methods:
DHCP
Factory default IP address and the web interface
Serial console interface on the CMC unit on the front of the HPE Adaptive Rack Cooling System
The network connection for the HPE Adaptive Rack Cooling System is located on the rear of the unit at
the top of the unit next to the transfer switch.
1. You can access the HPE Adaptive Rack Cooling System web interface by default in the following
ways, depending on the facility network.
If a DHCP server is available on the network, the HPE Adaptive Rack Cooling System defaults to
DHCP. The front panel of the HPE Adaptive Rack Cooling System shows the assigned IP address
on the information screen.
If DHCP is not available on the network, the HPE Adaptive Rack Cooling System defaults to the IP
address 192.168.0.190. To view the web interface, use a PC configured with the appropriate IP
settings.
34
Installation