Specifications; Hpe Adaptive Rack Cooling System Specifications - HPE ARCS 48U User Manual

Adaptive rack cooling system
Table of Contents

Advertisement

Specifications

HPE Adaptive Rack Cooling System specifications

Physical specifications
Item
Maximum height
Maximum width
Maximum depth (including the rack and rack
handle)
Maximum shipping height (on skid)
Maximum shipping width (on skid)
Maximum shipping depth (on skid)
Net weight
Shipping Weight (gross with packaging)
Electrical specifications
Item
Input voltage range
Effective cooling
Rated current maximum
Steady state current with maximum fans
Cooling medium
Permissible operating pressure max
Specification
200.7 cm (79 in)
60 cm (23.6 in) maximum
166 cm (65.3 in) (Depth includes front and rear
extensions)
228.5 cm (90.0 in)
122.0 cm (48.0 in)
182.9 cm (72.0 in)
645 kg (1,423 lb)
732 kg (1,614 lb)
Specification
380-480V, 3ph Wye (3P+N+Gnd)
150 Kw at 270 lpm (71 US gal/min)
380Y/220V: 17.5A
400Y/230V: 16.7A
415Y/240V: 16.0A
480Y/277V: 13.8A
380Y/220V: 13.0A
400Y/230V: 12.4A
415Y/240V: 11.9A
480Y/277V: 10.3A
Air and facility water/glycol
8 bar (116 psi)