Installing the HPE Adaptive Rack Cooling System

Procedure
1.
Read the unpacking instructions on the HPE Adaptive Rack Cooling System packaging material.
WARNING: The HPE Adaptive Rack Cooling System is shipped on a pallet and weighs
approximately 645 kg (1,423 lb) by itself or 732 kg (1,614lb) including packaging. Hewlett
Packard Enterprise recommends hiring professional movers to move the unit, remove the HPE
Adaptive Rack Cooling System from the pallet, and move the HPE Adaptive Rack Cooling
System to the final location.
2.
Using four or more people and the ramps that came with the HPE ARCS 42U/48U 600x1600mm
Rack, remove the HPE Adaptive Rack Cooling System from the pallet.
3.
Roll the HPE Adaptive Rack Cooling System to the final location.
CAUTION: Before attaching the hoses to the HPE Adaptive Rack Cooling System, verify that
the water supply and return are closed. Water that leaks into the unit can cause significant
damage.
4.
Install the hoses, differential pressure tube, and Panduit boots.
5.
To level the HPE Adaptive Rack Cooling System:
a. Remove the screws from the fan housing.
b. Unplug the fan communication and power cables.
c. Remove the lower fan from the rack.
CAUTION: Use a minimum of two people to manually move the fan.
d. Adjust the leveling feet using a bubble level.
Installation
23