Item
Maximum operating noise level (with IT rack doors
open)
Power cords
Thermal and air flow performance
Thermal and air flow performance
parameters
Air temperature—Inlet to rack-mounted
components
Chilled water temperature
Total rack-mounted component air flow
Chilled water flow rate
Chilled water pressure differential at flow
necessary to meet thermal specifications
Server heat load
Environmental specifications
Parameter
Room temperature:
Recommended minimum/maximum
Humidity:
Recommended range
Air quality
68
Specifications
Specification
101 dBa
IEC 60309 32/30A 220/415V 6h/IP44 (Quantity 2)
Maximum branch circuit size: 32A
NEMA L22-20P 277/480V 4P/5W (Quantity 2)
Maximum branch circuit size: 20A
Single rack
User adjustable up to 40ºC (104ºF)
7º-32°C (45º-89.6°F)
With 4 fans: up to 10,000 CFM (16,990 m3/h)
With 3 or 4 fans: 7,500 CFM (12,743 m3/h)
Operating 150 kW maximum
Performance is dependent on water temperature and air
temperature set point.
270 l/min (71.3 US gal/min)
15 psid
150 kW maximum
For more information, see "Determining heat load capacities"
in the HPE Adaptive Rack Cooling System Site Preparation
Guide.
Value
10°C (50°F)/50°C (122°F)
8% to 90% relative humidity, non-condensing
Standard Hewlett Packard Enterprise
requirements