Thermal And Air Flow Performance; Environmental Specifications - HPE ARCS 48U User Manual

Adaptive rack cooling system
Table of Contents

Advertisement

Item
Maximum operating noise level (with IT rack doors
open)
Power cords

Thermal and air flow performance

Thermal and air flow performance
parameters
Air temperature—Inlet to rack-mounted
components
Chilled water temperature
Total rack-mounted component air flow
Chilled water flow rate
Chilled water pressure differential at flow
necessary to meet thermal specifications
Server heat load

Environmental specifications

Parameter
Room temperature:
Recommended minimum/maximum
Humidity:
Recommended range
Air quality
68
Specifications
Specification
101 dBa
IEC 60309 32/30A 220/415V 6h/IP44 (Quantity 2)
Maximum branch circuit size: 32A
NEMA L22-20P 277/480V 4P/5W (Quantity 2)
Maximum branch circuit size: 20A
Single rack
User adjustable up to 40ºC (104ºF)
7º-32°C (45º-89.6°F)
With 4 fans: up to 10,000 CFM (16,990 m3/h)
With 3 or 4 fans: 7,500 CFM (12,743 m3/h)
Operating 150 kW maximum
Performance is dependent on water temperature and air
temperature set point.
270 l/min (71.3 US gal/min)
15 psid
150 kW maximum
For more information, see "Determining heat load capacities"
in the HPE Adaptive Rack Cooling System Site Preparation
Guide.
Value
10°C (50°F)/50°C (122°F)
8% to 90% relative humidity, non-condensing
Standard Hewlett Packard Enterprise
requirements

Advertisement

Table of Contents
loading

This manual is also suitable for:

Arcs 42u

Table of Contents