10. Verify that flow is shown in the Visualization screen. Be sure that flow rate is greater than 60 gpm.
11. Repeat steps 5-10, but return valves and fans to automatic operation instead of manual.
12. If there are any manual valves on the facility lines, be sure that they are open.
13. If necessary, use the bleeder tool from the accessory kit to open the bleeder valve and remove
trapped air from the heat exchanger. To verify that the heat exchanger is bleeding correctly, be sure
that a few drops of facility water pass through the tube.
56
Installation