5.9
The status of the digital signals can be read in decimal coding via the parameters
tal inputs
checking the various control signals and their connections with the software functions in
question, in particular in commissioning.
After conversion of the decimal figure into the binary system, bits 9 and 10 display the
states of the inputs EM-S2IND and EM-S3IND.
control signal 16
(decimal value 32768)
control signal 15
(
decimal value
control signal 14
(
decimal value
control signal 13
(
decimal value
control signal 12
(
decimal value
control signal 11
(
decimal value
control signal 10
(
decimal value
control signal 9
(
decimal value
Example:
The actual value parameter
conversion into the binary system, the following combination results:
Binary system:
control signal 10
(decimal value 512)
The following status of the digital input signals of the EM-IO-03 expansion module has
been displayed.
Note:
06/05
06/05

Status of the digital signals

Digital outputs
250 and
Coding of the status of the digital signals
Bit
15 14 1312 1110 9
16384)
8192)
4096)
2048)
1024)
512)
256)
Digital inputs
Bit
15 14 13 12 1110 9
0 0 0 0 0 0
Digital input EM-S2IND = 0 – control signal 9
Digital input EM-S3IND = 1 – control signal 10
The two digital inputs of the EM-IO-03 expansion module can be used for
the evaluation of a speed sensor via the parameter
Speed sensor 2
493. The control signals are set to the logical value zero
as a function of the selected operation mode.
254. The display of the digital input signals enables
Bit
8 7 6 5 4 3 2
250 displays the decimal value 640. After
Bit
7 6 5 4 3 2
8
1
0
1 0 0 0 0 0
Digi-
1
0
control signal 1
(
decimal value
1)
control signal 2
(
decimal value
2)
control signal 3
(
decimal value
4)
control signal 4
(
decimal value
8)
control signal 5
(
decimal value
16)
control signal 6
(
decimal value
32)
control signal 7
(
decimal value
64)
control signal 8
(
decimal value
128)
1
0
0
0
control signal 8
(decimal value 128)
Operation mode
67