30Xav-Ze 901; Multiple Chiller Installation; Distance To The Wall - Carrier AquaForce PUREtec 30XAV-ZE 401 Installation, Operation And Maintenance Instructions

Variable-speed air-cooled screw chillers with r1234ze (e)
Table of Contents

Advertisement

3.7 - 30XaV-ZE 901

legend:
All dimensions are given in mm.
Required clearances for maintenance (see note)
Recommended space for evaporator tube removal
Water inlet for standard unit
For options 100A, 100C, 107 refer to the certified drawing.
Water outlet for standard unit
For options 100A, 100C, 107 refer to the certified drawing.
Air outlet – do not obstruct
Power supply and control connection
C
Control circuit connection for option 158

3.8 - Multiple chiller installation

It is recommended to install multiple chillers in a single
row, arranged as shown in the example below, to avoid
recycling of warm air from one unit to another.
1.5 m
mini
If the situation at the site does not permit this arrangement,
contact your Carrier distributor to evaluate the various
possible arrangements. In certain situations an accessory
(supplied loose at the time of purchase) can be added.
1.5 m
mini
H
NOTES:
Drawings are not contractually binding.
Before designing an installation, consult the certified
dimensional drawings, available on request.
For the positioning of the fixing points, weight
distribution and centre of gravity coordinates please
refer to the dimensional drawings.
If any unit(s) are close to walls, please refer to
chapters 3.8 - 3.9 - "Distance to the wall" of this
document to determine the space required.

3.9 - distance to the wall

To ensure correct operation for most cases:
If h < H (2.3 m), minimum S = 3 m
If h > H or S < 3 m, contact your Carrier distributor to
evaluate the various possible arrangements. In certain
situations an accessory (supplied loose at the time of
purchase) can be added.
Anti-vibration
mounts
Wall
S
h
15