The CAN bus bard rate has the high relationship with the bus length. The
following table indicates the corresponding bus length on every kind of baud
rate.
Baud rate (bit/s)
Note: When the bus length is greater than 1000m, the
I-7188XBD-CAN/μPAC-7186EXD-CAN user manual (ver.1.0.3, May/09/2014)
Max. Bus length (m)
1 M
800 K
500 K
250 K
125 K
50 K
20 K
10 K
bridge or repeater devices may be needed.
25
50
100
250
500
1000
2500
5000
12