Hitachi SJ700-2 Series Instruction Manual page 88

Easy-sequence programming software ezsq
Hide thumbs Also See for SJ700-2 Series:
Table of Contents

Advertisement

Chapter 5 Instruction Words
Variable name
General-purpose analog output
YA (0)
General-purpose analog output
YA (1)
General-purpose analog output
YA (2)
(AMI terminal)
- Explanation
These variables can be used to monitor the data output to the FM, AM, and AMI terminals (analog
output terminals of the inverter) in a data range from 0% to 100.00%. To obtain the analog outputs, you
must assign general-purpose output functions to the FM, AM, and AMI terminals with inverter
parameters "C027", "C028", and "C029".
YA (0): FM output terminal
YA (1): AM output terminal
YA (2): AMI output terminal
- Sample program: Program to output inverter output frequency data to a general-purpose analog
output as data that is one-half of the full-scale data
  :
FW=
LOOP
UL(00)=
UL(00)=
UL(00)=
SET-Freq=
UL(01)=
UL(01)=
YA(1)=
goto
  :
(FM terminal)
(AM terminal)
(C027 = 12 [YA0])
(C028 = 13 [YA1])
(C029 = 14 [YA2])
1
XA(0)
UL(00) *
60
UL(00) /
100
UL(00)
FM
*
100
UL(01) /
60
UL(01) /
2
LOOP
Range of values
Default
0 to 10000
0
: Fetch analog input data.
: Convert the scale.
: Set the output frequency.
: Convert the scale.
: Output data that is one-half of the full-scale data.
5 - 34
Unit
Data size
Attribute
Unsigned
Readable
0.01 %
1-word
data
writable
and

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sj700 series

Table of Contents