Hitachi SJ700-2 Series Instruction Manual page 119

Easy-sequence programming software ezsq
Hide thumbs Also See for SJ700-2 Series:
Table of Contents

Advertisement

(2) A parameters
Display
Function name
code
DC braking carrier frequency
A059
setting
A061 Frequency upper limit setting
Frequency upper limit setting,
A261
2nd motor
A062 Frequency lower limit setting
Frequency lower limit setting,
A262
2nd motor
Jump (center) frequency setting
A063
1
Jump (hysteresis) frequency
A064
width setting 1
Jump (center) frequency setting
A065
2
Jump (hysteresis) frequency
A066
width setting 2
Jump (center) frequency setting
A067
3
Jump (hysteresis) frequency
A068
width setting 3
Acceleration stop frequency
A069
setting
Acceleration stop time frequency
A070
setting
A071 PID Function Enable
A072 PID proportional gain
A073 PID integral time constant
A074 PID derivative gain
A075 PV scale conversion
A076 PV source setting
A077 Output of inverted PID deviation 0(OFF), 1 (ON)
A079 PID feed forward selection
A078 PID variation range
A081 AVR function select
AVR voltage select
A082
A085 Operation mode selection
A086 Energy saving mode tuning
A092 Acceleration (2) time setting
Acceleration (2) time setting, 2nd
A292
motor
Acceleration (2) time setting, 3rd
A392
motor
A093 Deceleration (2) time setting
Deceleration (2) time setting,
A293
2nd motor
Deceleration (2) time setting, 3rd
A393
motor
Select method to switch to
A094
Acc2/Dec2 profile
Select method to switch to
A294
Acc2/Dec2, 2nd motor
Acc1 to Acc2 frequency
A095
transition point
Acc1 to Acc2 frequency
A295
transition point, 2nd motor
Dec1 to Dec2 frequency
A096
transition point
Dec1 to Dec2 frequency
A296
transition point, 2nd motor
A097 Acceleration curve selection
Range of setting
*2
0 or "1st minimum frequency limit" to "maximum
frequency"
0 or "2nd minimum frequency limit" to "maximum
frequency, 2nd motor"
0 or "start frequency" to "maximum frequency limit"
0 or "start frequency" to "maximum frequency, 2nd motor
limit"
0 to 40000
0 to 1000
0 to 40000
0 to 1000
0 to 40000
0 to 1000
0 to 40000
0 to 600
0 (disabling), 1 (enabling),
2 (enabling inverted-data output)
2 to 50
0 to 36000
0 to 10000
1 to 9999
0 (input via OI), 1 (input via O), 2 (external
communication), 3 (pulse-string frequency input), 10
(operation result output)
0 (disabled), 1 (O input), 2 (OI input), 3 (O2 input)
0 to 1000
0 (always on), 1 (always off),02 (off during deceleration)
200 V class: 0(200),1(215),2(220),3(230),4(240)
400 V class: 5(380),6(400),7(415),8(440),9(460),10(480)
0 (normal operation), 1 (energy-saving operation),
2 (fuzzy operation)
1 to 1000
1 to 360000
1 to 360000
1 to 360000
1 to 360000
1 to 360000
1 to 360000
0 (switching by 2CH terminal), 1 (switching by setting),
2 (switching only when rotation is reversed)
0 (switching by 2CH terminal), 1 (switching by setting),
2 (switching only when rotation is reversed)
0 to 40000
0 to 40000
0 to 40000
0 to 40000
0 (linear), 1 (S curve), 2 (U curve),
3 (inverted-U curve), 4 (EL-S curve)
8 - 3
Chapter 8 Appendix
Setting during
Updating during
Minimum
operation
operation
unit
(allowed or not)
(allowed or not)
×
×
0.1 (kHz)
×
0.01 (Hz)
×
0.01 (Hz)
×
0.01 (Hz)
×
0.01 (Hz)
×
0.01 (Hz)
×
0.01 (Hz)
×
0.01 (Hz)
×
0.01 (Hz)
×
0.01 (Hz)
×
0.01 (Hz)
×
0.01 (Hz)
×
0.1 (s)
×
0.1
0.1 (s)
0.01 (s)
×
0.01
×
×
×
×
0.1 (%)
×
×
×
×
×
×
0.1 (%)
0.01 (s)
0.01 (s)
0.01 (s)
0.01 (s)
0.01 (s)
0.01 (s)
×
×
×
×
×
×
0.01 (Hz)
×
×
0.01 (Hz)
×
×
0.01 (Hz)
×
×
0.01 (Hz)
×
×

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sj700 series

Table of Contents