Parameter
Function of the
code
parameter
02-07
Low voltage level
02-08
PTC action selection
02-09
PTC level
02-10
PTC detection filtering time 0.00~10.00 seconds
02-11
PTC type
02-12
Motor fan activation level
Electronic thermal relay
02-13
selection 1
Electronic thermal
02-14
characteristic for motor
Output frequency at
02-15
malfunction
Output voltage at
02-16
malfunction
02-17
DC voltage at malfunction
Output current at
02-18
malfunction
IGBT temperature at
02-19
malfunction
Settings
45: PG slip error (PGF4)
46: Reserved
47: Reserved
48: Reserved
49: External fault input (EF)
50: Emergency stop (EF1)
51: Reserved
52: Password error(PcodE)
53: Reserved
54: Communication error (cE1)
55: Communication error (cE2)
56: Communication error (cE3)
57: Communication error (cE4)
58:Communication time out (cE10)
59: PU time out (cP10)
60: Braking transistor error (bF)
61~63: Reserved
64: Safety relay Error (SRY)
65: PG card information error (PGF5)
66: Over pressure (ovP)
67: Pressure feedback fault (PfbF)
160.0~220.0Vdc
320.0.0~440.0Vdc
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
0.0~150.0%
0.0~150.0℃
0: Not assigned
1: KTY84
0.0~100.0%
0.0~150.0℃
0: Inverter motor
1: Standard motor
2: Disable
30.0~600.0 seconds
0.00~655.35 Hz
0.0~6553.5 V
0.0~6553.5 V
0~655.35 Amps
0.0~6553.5 ℃
4-9
Chapter 4 Parameter Functions
Default
value
180.0
360.0
50.0
0.20
50.0
60.0
Read only ○
Read only ○
Read only ○