Chapter 2 Wiring|HES Series
Terminal
Analog Voltage
AUI
AFM
ACM
Analog control signal (common)
Analog Input Terminals (PO, PI, QI, AUI, ACM)
The maximum input voltage of PI, PO, and QI cannot exceed +12V and no more than +/-12V
for AUI. Otherwise, the analog input function may become ineffective.
Analog input signals are easily affected by external noise. Use shielded wiring and keep it as
short as possible (<20m) with proper grounding. If the noise is inductive, connecting the shield
to terminal ACM can bring improvement.
The interference generated by the Hybrid Servo Controller can cause the pressure sensor to
malfunction. IN this case, a capacitor and a ferrite core can be connected to the pressure
sensor side, as shown in the figure below:
Transistor outputs (MO1, MO2, MCM)
Make sure to connect the digital outputs to the right polarity.
When connecting a relay to the digital outputs connect a surge absorber across the coil and
check the polarity.
Function
AUI circuit
+10V
AUI
-10V
Internal Circuit
AFM
ACM
*Control signal wiring size: 18 AWG (0.75 mm
Threaded for three rounds or
more in the sam e phase
Output
term inal
-V
Factory Setting (NPN mode)
Impedance:11.3kΩ
Resolution:12 bits
Range:-10~+10VDC
Impedance:16.9kΩ (voltage output)
Output Current: 20mA max
Resolution: 0~10V corresponds to maximum operation
frequency
Range: 0~10V
Function Setting: Pr.00-05
Common for ACI, AUI1, AUI2
PO
C
ACM
Ferrite core
2-16
2
) with shielded wire.