Line Modules
4.3 Active Line Modules
Order number
Degree of protection
Dimensions
- Width
- Height
- Depth
Degree of protection
Frame size
Weight
UL listed fuse
4)
- Number (connected in parallel)
- Rated current
- Frame size acc. to IEC 60269
Valid for a 5 s duty cycle (overload duration) and a duty cycle duration of 300 s based on the base load DC link current.
1)
The specified power loss is the maximum value at 100 % capacity utilization. In normal operation a lower value is
2)
established.
This value applies to the water coolant option; for other coolant types, see Chapter "Cooling circuit and coolant
3)
properties".
To achieve a UL-approved system, it is absolutely essential to use the fuse types specified in the table.
4)
130
6SL3335–
7TG35–8AA3
IP00
mm
265
mm
1002
mm
545
IP00
HXL
kg
110
3NE1447-2
1
A
670
3
7TG41–3AA3
IP00
295
1516
545
IP00
JXL
220
3NE1438-2
2
800
3