Motor Modules
5.3 Interface description
5.3.4

X9 terminal strip

Table 5- 3
Terminal strip X9
Terminal
1
1
2
2
3
4
5
6
7
8
Max. connectable cross-section 1.5 mm
NOTICE
The function of the EP terminals is only available when Safety Integrated Basic Functions
are enabled.
Note
The two "P24 V" or "M" terminals are jumpered in the connector. This ensures that the
supply voltage is looped through, even when the connector is removed.
144
Signal name
P24 V
P24 V
M
M
VL1
VL2
HS1
HS2
EP +24 V (Enable Pulses)
EP M1 (Enable Pulses)
2
Technical specifications
Voltage: 24 V DC (20.4 V – 28.8 V)
Power consumption: See Technical data
240 V AC: 8 A max.
24 V DC: max. 1 A
isolated
240 V AC: 8 A max.
24 V DC: max. 1 A
isolated
Supply voltage: 24 V DC (20.4 V - 28.8 V)
Power consumption: 10 mA
Signal propagation times:
L → H: 100 μs
H → L: 1000 µs
The pulse disable function is only available when Safety
Integrated Basic Functions are enabled.