Motor Modules
5.6 Technical specifications
Order number
Max. conductor cross-sections
- DC link connection (DCP, DCN)
- Motor connection (U2, V2, W2)
- PE connection
Max. cable length
Degree of protection
Dimensions
- Width
- Height
- Depth
Frame size
Weight
UL listed fuse
5)
- Number (connected in parallel)
- Rated current
- Frame size acc. to IEC 60269
Rated output of a typical 6-pole standard induction motor based on I
1)
Rated output of a typical 6-pole standard induction motor based on I
2)
The specified power loss is the maximum value at 100% capacity utilization. In normal operation a lower value is
3)
established.
This value applies to the water coolant option; for other coolant types, see Chapter "Cooling circuit and coolant
4)
properties".
To achieve a UL-approved system, it is absolutely essential to use the fuse types specified in the table.
5)
156
6SL3325– 1TE32-1AA3
mm²
Busbar
mm²
2 x 95
mm²
2 x 95
m
IP00
mm
150
mm
746
mm
545
FXL
kg
41
3NE3230-0B
1
A
315
1
or I
L
or I
L
1TE32–6AA3
1TE33-1AA3
Busbar
Busbar
2 x 95
2 x 240
2 x 95
2 x 240
300 (shielded) / 450 (unshielded)
IP00
IP00
150
150
746
1172
545
545
FXL
GXL
41
80
3NE3232-0B
3NE3233
1
1
400
450
1
1
at 400 V 3 AC 50 Hz.
H
at 460 V 3 AC 60 Hz.
H
Chassis Liquid Cooled Power Units
Manual, (GH7), 01/2011, 6SL3097-4AM00-0BP1
1TE35–0AA3
Busbar
2 x 240
2 x 240
IP00
150
1172
545
GXL
80
3NE3336
1
650
2

Advertisement