Derating Factors As A Function Of Coolant Temperature - Siemens SINAMICS S120 Equipment Manual

Chassis liquid cooled power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules
4.2 Basic Line Modules
4.2.7.1

Derating factors as a function of coolant temperature

SINAMICS S120 Liquid Cooled units are designed for cooling by H
Antifrogen N mixture. An H
Antifrogen N.
When H
between 5 °C and 45 °C. The maximum output current decreases linearly to 90 % at
temperatures between 45 °C and 50 °C.
When H
100 % output current at temperatures between 0 °C and 45 °C. The maximum output current
decreases linearly to 90 % at temperatures between 45 °C and 50 °C.
Figure 4-9
104
O Antifrogen N mixture must contain between 20 % and 45 %
2
O is used as a coolant, the units can supply 100 % output current at temperatures
2
O Antifrogen N mixture described above is used as a coolant, the units can supply
2
Maximum output current as a function of coolant temperature
O or by an H
2
Chassis Liquid Cooled Power Units
Manual, (GH7), 01/2011, 6SL3097-4AM00-0BP1