Cooling Circuit Configuring Information - Siemens SINAMICS S120 Equipment Manual

Chassis liquid cooled power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Figure 8-3
8.1.4

Cooling circuit configuring information

The operating pressure must be set according to the flow conditions in the supply and return
lines of the cooling circuit. The required coolant flow rate per time unit must be set according
to the technical data of the devices. The units are normalized to a rated pressure of 70 kPa
(for coolant type H
If a mixture of Antifrogen N and H
calculated according to the mixing ratio. The following table specifies the pressure drop
across components at different coolant temperatures for a coolant with mixing ratio 45 %
Antifrogen N.
The maximum permissible pressure to atmosphere in the heat sink and thus in the cooling
circuit must not exceed 6 bar. If the pump used can reach a maximum pressure in excess of
this value, appropriate measures (safety valve p ≤ 6 bar, pressure control or similar) must be
implemented by the customer to ensure that the maximum pressure limit is not exceeded.
The lowest possible differential pressure between the coolant in the supply and return lines
should be selected to allow use of pumps with a flat characteristic.
The maximum differential pressure across a heat sink is 200 kPa; higher differential
pressures significantly increase the risk of cavitation and abrasion.
Chassis Liquid Cooled Power Units
Manual, (GH7), 01/2011, 6SL3097-4AM00-0BP1
Arrangement of pressure compensator, component pressure drops
O) via an orifice.
2
O is used as a coolant, the rated pressure must be
2
Cooling circuit and coolant properties
8.1 Cooling circuits
231