4 AutomationDrive FC 300 Selection
Line Power Supply 3 x 525–690 V AC
AutomationDrive FC
302
High/ Normal Load*
4
Max. input current
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
4-18
P630
HO
Typical Shaft output at
550 V [kW]
500
Typical Shaft output at
575 V [HP]
650
Typical Shaft output at
690 V [kW]
630
Enclosure IP21, 54
without/with options
F1/ F3
cabinet
Output current
Continuous
659
(at 550 V) [A]
Intermittent (60 sec
overload)
989
(at 550 V) [A]
Continuous
630
(at 575/690 V) [A]
Intermittent (60 sec
overload)
945
(at 575/690 V) [A]
Continuous KVA
628
(at 550 V) [KVA]
Continuous KVA
627
(at 575 V) [KVA]
Continuous KVA
753
(at 690 V) [KVA]
Continuous
642
(at 550 V) [A]
Continuous
613
(at 575 V) [A]
Continuous
613
(at 690 V) [A]
Max. cable size, motor
2
2)
[mm
(AWG
)]
Max. cable size, line
power F1/F2 [mm
2
(AWG
2)
)]
Max. cable size, line
power F3/F4 [mm
2
(AWG
2)
)]
Max. cable size, load-
2
2)
sharing [mm
(AWG
)]
Max. cable size, brake
[mm
2
(AWG
2)
)
Max. external electrical
1
fuses [A]
Estimated power loss
9201
at 600 V [W]
4)
Estimated power loss
9674
4)
at 690V [W]
F3/F4 Max added los-
ses CB or Disconnect &
342
Contactor
Max panel options los-
ses
Weight,
enclosure IP21, IP 54
1004/ 1299
[kg]
Weight, Rectifier Mod-
102
ule [kg]
Weight, Inverter Mod-
102
ule [kg]
4)
Efficiency
Output frequency
Heatsink overtemp. trip
Power card ambient
trip
MG.33.BC.22 - VLT
P710
P800
NO
HO
NO
HO
560
560
670
670
750
750
950
950
710
710
800
800
F1/ F3
F1/ F3
763
763
889
889
839
1145
978
1334
730
730
850
850
803
1095
935
1275
727
727
847
847
727
727
847
847
872
872
1016
1016
743
743
866
866
711
711
828
828
711
711
828
828
8x150
(8x300 mcm)
8x240
(8x500 mcm)
8x456
(8x900 mcm)
4x120
(4x250 mcm)
4x185
(4x350 mcm)
1600
10771
10416
12272
12260
11315
10965
12903
12890
427
419
532
519
400
1004/ 1299
1004/ 1299
102
102
0.98
0–500 Hz
185°F [85°C]
154°F [68°C]
®
is a registered Danfoss trademark
FC 300 Design Guide
P900
NO
HO
NO
HO
750
750
850
850
1050
1050
1150
1150
900
900
1000
1000
F2/ F4
988
988
1108
1108
1087
1482
1219
1662
945
945
1060
1060
1040
1418
1166
1590
941
941
1056
1056
941
941
1056
1056
1129
1129
1267
1267
962
962
1079
1079
920
920
1032
1032
920
920
1032
1032
12x150
(12x300 mcm)
6x185
(6x350 mcm)
13835
13755
15592
15107
14533
14457
16375
15899
615
556
665
634
1246/ 1541
1246/ 1541
102
136
136
102
P1M0
NO
1000
1350
1200
F2/ F4
1317
1449
1260
1386
1255
1255
1506
1282
1227
1227
2000
18281
19207
863
136
102

Advertisement

Table of Contents
loading

Table of Contents