FC 300 Design Guide
11.8.8 Coil Register Addressing
In Modbus, all data are organized in coils and holding registers. Coils hold a single bit, whereas holding registers hold a 2-byte word (i.e., 16 bits). All
data addresses in Modbus messages are referenced to zero. The first occurrence of a data item is addressed as item number zero. For example: The coil
known as 'coil 1' in a programmable controller is addressed as coil 0000 in the data address field of a Modbus message. Coil 127 decimal is addressed
as coil 007EHEX (126 decimal).
Holding register 40001 is addressed as register 0000 in the data address field of the message. The function code field already specifies a 'holding register'
operation. Therefore, the '4XXXX' reference is implicit. Holding register 40108 is addressed as register 006BHEX (107 decimal).
Coil Number
Description
1-16
Adjustable frequency drive control word (see table below)
17-32
Adjustable frequency driver speed or setpoint reference Range 0x0–0xFFFF (-200% ...
~200%)
33-48
Adjustable frequency drive status word (see table below)
49-64
Open-loop mode: adjustable frequency drive output frequency Closed-loop mode: Ad-
justable frequency drive feedback signal
65
Parameter write control (master to slave)
0 =
1 =
66-65536
Reserved
Coil
0
01
Preset reference LSB
02
Preset reference MSB
03
DC brake
04
Coast stop
05
Quick stop
06
Freeze freq.
07
Ramp stop
08
No reset
09
No jog
10
Ramp 1
11
Data not valid
12
Relay 1 off
13
Relay 2 off
14
Set up LSB
15
Set up MSB
16
No reversing
Adjustable frequency drive control word (FC profile)
Parameter changes are written to the RAM of the adjustable frequency
drive.
Parameter changes are written to the RAM and EEPROM of the adjust-
able frequency drive.
1
No DC brake
No coast stop
No quick stop
No freeze freq.
Start
Reset
Jog
Ramp 2
Data valid
Relay 1 on
Relay 2 on
Reversing
MG.33.BC.22 - VLT
®
is a registered Danfoss trademark
11 RS-485 Installation and Set-up
Signal Direction
Master to slave
Master to slave
Slave to master
Slave to master
Master to slave
Coil
0
33
Control not ready
34
Adjustable frequency drive
not ready
35
Coasting stop
36
No alarm
37
Not used
38
Not used
39
Not used
40
No warning
41
Not at reference
42
Hand mode
43
Out of freq. range
44
Stopped
45
Not used
46
No voltage warning
47
Not in current limit
48
No thermal warning
Adjustable frequency drive status word (FC profile)
1
Control ready
Adjustable frequency drive
ready
Safety closed
Alarm
Not used
Not used
Not used
Warning
At reference
Auto mode
In frequency range
Running
Not used
Voltage warning
Current limit
Thermal warning
11-15
11