FC 300 Design Guide
11 RS-485 Installation and Set-up
11.4.4 Adjustable Frequency Drive Address (ADR)
Two different address formats are used.
The address range of the adjustable frequency drive is either 1-31 or 1-126.
1. Address format 1-31:
Bit 7 = 0 (address format 1-31 active)
Bit 6 is not used
Bit 5 = 1: Broadcast, address bits (0-4) are not used
Bit 5 = 0: No Broadcast
Bit 0-4 = Adjustable frequency drive address 1-31
2. Address format 1-126:
Bit 7 = 1 (address format 1-126 active)
Bit 0-6 = Adjustable frequency drive address 1-126
Bit 0-6 = 0 Broadcast
The slave returns the address byte unchanged to the master in the response telegram.
11.4.5 Data Control Byte (BCC)
The checksum is calculated as an XOR-function. Before the first byte in the telegram is received, the calculated checksum is 0.