5.2.4 Switches, jumpers and LED
Switch
V/I settings on inputs and analog output
Analog input 1
S1
Default = voltage (
Analog input 2
S2
Default = voltage (
Analog output 2
S3
Default = voltage (
Jumpers
HC0
Reserved. Deafult = Open
HC1
Open = 690 Vac rated voltage (default)
Closed =
575 Vac rated voltage (ADV-7... sizes)
CFG
690 Vac rated voltage (ADV-5... and ADV-6... sizes)
Jumpers :
Switches :
S1
±10 V)
±10 V)
±10 V)
ADV200 • Quick start up guide - Specification and installation
HC0
HC1
CFG
LEDs :
S1
V
I
S2
S3
LEDs
PWM
LED lit during IGBT modulation
(green)
Flashes (freq. 1 sec) if no errors or faults
RUN
have occurred.
(green)
If ON or OFF, indicates an error conditions
(software hangup)
PWR
ON when the regulation card is correctly
(green)
powered
Function
PWM
RUN
PWR
S2
S3
V
I
V
Function
I
43