Practical example
The following examples illustrate the philosophies and methods with which more
or less complex operations are performed in the single "function blocks", the
results of which represent the output of the block.
• Example: Changing the Speed Reference source
The main drive reference (in the default configuration) Ramp ref 1 mon (PAR:
620) is generated by the output of the function block "Ramp setpoint Block".
Its default source is the Analog input 1 mon signal (PAR: 1500), from the output
of the function block "Analog input 1 Block", which in this case refers to analog
input 1 of the signal terminal strip.
To change the reference source from the analog input to a digital reference inside
the drive, the input signal must be changed to "Ramp setpoint Block".
Enter the Ramp ref 1 src parameter (PAR: 610) and set a new reference, select-
ing it from among those listed in the L_MLTREF selection list, for example Dig
ramp ref 1 (PAR: 600).
• Example: Inverting the analog reference signal
To invert the "Analog input 1 Block" output signal, the value of the An inp 1 sign
src parameter (PAR: 1526), which has a default setting of Null (no operation),
must be changed by selecting the source of the command signal from among
those listed in the L_DIGSEL 2 selection list, for example Digital input X mon,
One (function always enabled), etc.
Terminal input
Ramp ref 1 src
Ramp ref invert src
Null
The diagrams above illustrate the internal processing philosophy of the single
"function blocks" and the result of these changes on the other interconnected
"function blocks".
Analog input 1 Block
An inp 1 sign src
Null
Ramp Setpoint Block
ADV200 • Quick start up guide - Specification and installation
* -1
* +1
An inp 1 alt value
Null
An inp 1 alt sel src
+1
-1
Analog input 1 mon
Ramp ref 1 mon
105