Settings - Siemens SIPROTEC 4 7SD80 Manual

Line differential protection
Table of Contents

Advertisement

Characteristic Curves for the 50N Element
During configuration of the scope of functions at address 126, the available characteristics were determined.
Depending on the selection made there, only the parameters associated with this characteristic curve are
accessible.
The inverse time elements enable the user to select different characteristic curves. Address 126 allows you to
specify whether you work with IEC characteristics 50(N) 51(N) IEC or ANSI characteristics 50(N)
51(N)ANSI).
Bei den stromabhängigen Stufen können verschiedene Kennlinien gewählt werden. Unter Adresse 126 stellen
Sie ein, ob Sie mit IEC-Kennlinien (50(N) 51(N) IEC) oder ANSI-Kennlinien arbeiten (50(N) 51(N)ANSI).
If you work with IEC characteristics, you can select the following setting options at address 2642:
Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
If you work with ANSI characteristics, you can select the following setting options at address 2643:
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
The characteristics and equations they are based on are listed in the "Technical Data". They apply for direc-
tional and non-directional elements alike.
2.4.5

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding
secondary nominal current of the current transformer.
Addr.
Parameter
2603A
67N dir. meas.
2610
Op.Mode50(N)-B1
2610
Op.Mode67(N)-B1
2611
67(N)-B1 Dir.
2612
67(N)-B1 on FFM
2613
50-B1 PICKUP
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
C
Setting Options
V0/I0 or V2/I2
with V0/I0
with V2/I2
ON
Only Emer. prot
OFF
ON
Only Emer. prot
OFF
Non-Directional
Forward
Reverse
Non-Directional
BLOCKED
1A
0.10 .. 25.00 A; ∞
5A
0.50 .. 125.00 A; ∞
Default Setting
Comments
V0/I0 or V2/I2
67N, Measurement of
direction
OFF
Operating Mode 50(N)-B1
OFF
Operating Mode 67(N)-B1
Non-Directional
67(N)-B1 Direction
BLOCKED
67(N)-B1 Direct. stage on
Fuse Failure
2.00 A
50-B1 Pickup
10.00 A
Functions
2.4 Backup overcurrent
85