2.1 General
Spontaneous Messages on the Display
You can determine whether or not the most important data of a fault event is displayed automatically after
the fault has occurred (see also Subsection "Fault Messages" in Section "Auxiliary Functions").

Setting Notes

2.1.2.2
Fault Display
A new pickup by a protection element generally turns off any previously lit LEDs so that only the latest fault is
displayed at any one time. It can be selected whether the stored LED displays and the spontaneous fault indi-
cations on the display appear upon the new pickup, or only after a new trip signal is issued. In order to select
the desired displaying mode, select the submenu Device in the SETTINGS menu. Under address 610
FltDisp.LED/LCD the two alternatives Target on PU and Target on TRIP ("No trip – no flag") can be
selected.
Use parameter 615 Spont. FltDisp. to specify whether or not a spontaneous fault message should appear
automatically on the display (YES) or not (NO).
Selection of Default Display
The start page of the default display appearing after startup of the device can be selected in the device data
via parameter640 Start image DD. The pages available for each device version are listed in the Appendix
E Default Settings and Protocol-dependent
Protection Interface Test Mode
To check the communication quality of the two 7SD80 devices during commissioning, set parameter 650 PDI
Test Mode to ON. The availability of the communication link via the protection interface is displayed as a stat-
istical value (see Section
2.1.2.3

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
Addr.
Parameter
610
FltDisp.LED/LCD
615
Spont. FltDisp.
625A
T MIN LED HOLD
640
Start image DD
650
PDI Test Mode
2.1.2.4

Information List

No.
Information
-
Test mode
34
Functions.
2.17.2
Statistics).
Setting Options
Target on PU
Target on TRIP
NO
YES
0 .. 60 min
image 1
image 2
image 3
image 4
image 5
image 6
image 7
image 8
OFF
ON
Type of
Comments
Informa-
tion
IntSP
Test mode
Default Setting
Comments
Target on PU
Fault Display on LED / LCD
NO
Spontaneous display of flt.annun-
ciations
0 min
Minimum hold time of latched
LEDs
image 1
Start image Default Display
OFF
PDI Test Mode
E50417-G1100-C474-A2, Edition 02.2018
SIPROTEC 4, 7SD80, Manual