F.2 Settings
Addr. Parameter
3912
50NBF PICKUP
3913
T2StartCriteria
3921
End Flt. elem.
3922
EndFault Delay
4001
FCT 74TC
4002
No. of BI
4003
Alarm Delay
4201
FCT 49
4202
49 K-FACTOR
4203
TIME CONSTANT
4204
49 Θ ALARM
4205
I ALARM
4206
CALC. METHOD
4501
PDI FO
4502
PDI FO TER
4503
PDI FO level
4510
TD-DATA DISTURB
4512
Td ResetRemote
4601
PDI Cu
4602
PDI Cu TER
4603
PDI Cu mode
4604
PDI Cu MAX ATT
4605
PDI Cu S/N
4701
ID OF MASTER
350
Function
C
Setting Options
50BF BkrFailure 1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
50BF BkrFailure
With exp. of T1
Parallel withT1
50BF BkrFailure
ON
OFF
50BF BkrFailure
0.00 .. 30.00 sec; ∞ 2.00 sec
74TC TripCirc.
ON
OFF
74TC TripCirc.
1 .. 2
74TC TripCirc.
1 .. 30 sec
49 Th.Overload
OFF
ON
Alarm Only
49 Th.Overload
0.10 .. 4.00
49 Th.Overload
1.0 .. 999.9 min
49 Th.Overload
50 .. 100 %
49 Th.Overload 1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
49 Th.Overload
Θ max
Average Θ
Θ from Imax
Prot.Interface
ON
OFF
Prot.Interface
0.5 .. 20.0 %
Prot.Interface
-30 .. -10 dBm
Prot.Interface
0.05 .. 2.00 sec
Prot.Interface
0.00 .. 300.00 sec;
Prot.Interface
ON
OFF
Prot.Interface
0.5 .. 20.0 %
Prot.Interface
01
02
03
04
05
06
Prot.Interface
0 .. 46 dB
Prot.Interface
6 .. 30 dB
Diff.-Topo
1 .. 65534
Default Setting
Comments
0.10 A
50NBF Pickup neutral
current threshold
0.50 A
Parallel withT1
T2 Start Criteria
OFF
End fault element
Trip delay of end fault
element
OFF
74TC TRIP Circuit Supervi-
sion
2
Number of Binary Inputs
per trip circuit
2 sec
Delay Time for alarm
OFF
49 Thermal overload
protection
1.10
49 K-Factor
100.0 min
Time Constant
90 %
49 Thermal Alarm Stage
1.00 A
Current Overload Alarm
Setpoint
5.00 A
Θ max
Method of Acquiring
Temperature
ON
Protection Data Interface
fibre optic
1.0 %
PDI FO max. telegram
error rate
-28 dBm
PDI FO min. receive level
0.10 sec
Time delay for data
disturbance alarm
0.00 sec
Remote signal RESET
DELAY for comm.fail
ON
Protection Data Interface
copper
1.0 %
PDI Cu max. telegram
error rate
01
PDI Cu operation mode
46 dB
PDI Cu maximum attenu-
ation
6 dB
PDI Cu min signal to noise
ratio
1
Identification number of
Master
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018

Advertisement

Table of Contents
loading

Table of Contents