Siemens SIPROTEC 4 7SD80 Manual page 207

Line differential protection
Table of Contents

Advertisement

Setting Group Change
If binary inputs are used to switch setting groups, please observe the following:
Two binary inputs must be dedicated to the purpose of changing setting groups when four groups are to
be switched. One binary input must be set for
Bit1 . If either of these input functions is not assigned, then it is considered as not controlled.
For the control of 2 setting groups one binary input is sufficient, namely
non-assigned binary input
The control signals must be permanently active so that the selected setting group is and remains active.
The following table shows the allocation of the binary inputs to the setting groups A to D and a simplified
connection diagram for the two binary inputs is illustrated in the following figure. The figure illustrates an
example in which both Set Group Bits 0 and 1 are configured to be controlled (actuated) when the associated
binary input is energized (high).
Where:
no =
yes =
Table 3-1
>Param.Wahl1
[einstellgruppenumschaltung-ueber-binaere-160502-wlk, 1, en_US]
Figure 3-1
Trip Circuit Supervision 74TC
It must be noted that two binary inputs or one binary input and one bypass resistor R must be connected in
series. The pick-up threshold of the binary inputs must therefore be substantially below half the rated control
DC voltage.
If two binary inputs are used for the trip circuit supervision, these binary inputs must be isolated, i.o.w. not be
communed with each other or with another binary input.
If one binary input is used, a bypass resistor R must be used (refer to Figure 3-2). This resistor R is connected in
series with the second circuit breaker auxiliary contact (Aux2), to also allow the detection of a trip circuit
failure when the circuit breaker auxiliary contact 1 (Aux1) is open, and the command relay contact has reset.
The value of this resistor must be such that in the circuit breaker open condition (therefore Aux1 is open and
Aux2 is closed) the circuit breaker trip coil (TC) is no longer picked up and binary input (BI1) is still picked up if
the command relay contact is open.
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
>Set Group Bit1 is then regarded as not connected.
not energized or not connected
energized
Changing setting groups using binary inputs
Binary Input
no
yes
no
yes
Connection diagram (example) for setting group switching using binary inputs
>Set Group Bit0 , the other input for >Set Group
>Param. Wahl2
no
no
yes
yes
Mounting and Commissioning
3.1 Mounting and Connections
>Set Group Bit0 , since the
Active Group
Group A
Group B
Group C
Group D
207

Advertisement

Table of Contents