Siemens SIPROTEC 4 7SD80 Manual page 339

Line differential protection
Table of Contents

Advertisement

Addr. Parameter
625A
T MIN LED HOLD
640
Start image DD
650
PDI Test Mode
1103
FullScaleVolt.
1104
FullScaleCurr.
1107
P,Q sign
1130A PoleOpenCurrent
1131A PoleOpenVoltage
1132A SI Time all Cl.
1133A T DELAY SOTF
1134
Line Closure
1135
Reset Trip CMD
1150A SI Time Man.Cl
1152
Man.Clos. Imp.
1201
87L PCC-Prot.
1202
87L Idyn>
1203
87L Idyn close>
1204
87L Isteady>
1205
87L I min
1206
87L Trip Delay
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Function
C
Setting Options
Device, General
0 .. 60 min; ∞
Device, General
image 1
image 2
image 3
image 4
image 5
image 6
image 7
image 8
Device, General
OFF
ON
P.System Data
0.4 .. 500.0 kV
2
P.System Data
10 .. 20000 A
2
P.System Data
not reversed
2
reversed
P.System Data
1A
0.05 .. 1.00 A
2
5A
0.25 .. 5.00 A
P.System Data
2 .. 70 V
2
P.System Data
0.01 .. 30.00 sec
2
P.System Data
0.05 .. 30.00 sec
2
P.System Data
only with ManCl
2
I OR V or ManCl
52a OR I or M/C
I or Man.Close
P.System Data
CurrentOpenPole
2
Current AND 52a
Pickup Reset
P.System Data
0.01 .. 30.00 sec
2
P.System Data
(Einstellmöglich-
2
keiten anwendung-
sabhängig)
87 Diff. Prot.
OFF
ON
87 Diff. Prot.
1A
0.20 .. 20.00 A; ∞
5A
1.00 .. 100.00 A; ∞ 1.65 A
87 Diff. Prot.
1A
0.20 .. 20.00 A; ∞
5A
1.00 .. 100.00 A; ∞ 1.65 A
87 Diff. Prot.
1A
0.50 .. 20.00 A; ∞
5A
2.50 .. 100.00 A; ∞ 6.65 A
87 Diff. Prot.
1A
0.10 .. 20.00 A; ∞
5A
0.50 .. 100.00 A; ∞ 5.00 A
87 Diff. Prot.
0.00 .. 0.10 sec
Functions, Settings, Information
Default Setting
Comments
0 min
Minimum hold time of
latched LEDs
image 1
Start image Default
Display
OFF
PDI Test Mode
10.0 kV
Measurem:FullScale-
Voltage(Equipm.rating)
400 A
Measurem:FullScaleCur-
rent(Equipm.rating)
not reversed
P,Q operational measured
values sign
0.10 A
Pole Open Current
Threshold
0.50 A
30 V
Pole Open Voltage
Threshold
0.10 sec
Seal-in Time after ALL
closures
0.25 sec
minimal time for line
open before SOTF
only with ManCl
Recognition of Line
Closures with
CurrentOpenPole
RESET of Trip Command
0.30 sec
Seal-in Time after
MANUAL closures
none
MANUAL Closure Impulse
after CONTROL
ON
Phase current comparison
protection
0.33 A
Dynamic trip threshold
0.33 A
Dynamic trip threshold
line closure
1.33 A
Steady pick up threshold
1.00 A
Minimal phase current
0.00 sec
Trip Delay
F.2 Settings
339