Siemens SIPROTEC 4 7SD80 Manual page 26

Line differential protection
Table of Contents

Advertisement

Introduction
1.3 Characteristics
Time Overcurrent Protection
Optionally selectable as emergency function during protection data communication failure or as backup
function or both
A maximum of 3 definite time elements and one inverse time element, each for phase currents and
ground current
A maximum of 2 directional definite time elements and one directional inverse time element, each for
phase currents and ground current
For inverse time overcurrent protection, selection from various characteristics of different standards
possible
Blocking options e.g. for reverse interlocking with any element
Instantaneous tripping when closing onto a short circuit possible with any element
Inrush Current Restraint
Insensitive to inrush currents and against higher-frequency transients
High stability also for different current transformer saturation
Circuit-Breaker Failure Protection
With independent current elements for the monitoring of the current flow through each pole of the
circuit breaker
Separate pickup thresholds for phase and ground currents
Monitoring time element for tripping
Initiation by the trip command of each integrated protection function
Initiation by external trip functions possible
Single-element or two-element
No dropout and seal-in times
Thermal Overload Protection
Thermal replica of the current heat losses of the protected object
RMS measurement for all three phase currents
Adjustable thermal and current-dependent warning elements
Voltage Protection
Overvoltage and undervoltage detection with different elements
2 overvoltage elements for the phase-to-ground voltages
2 overvoltage elements for the phase-to-phase voltages
2 overvoltage elements for the positive sequence voltage
2 overvoltage elements for the negative sequence system of the voltages
2 overvoltage elements for the zero system of the voltages or for any other single-phase voltage
Adjustable dropout conditions
2 undervoltage elements for the phase-to-ground voltages
2 undervoltage elements for the phase-to-phase voltages
2 undervoltage elements for the positive sequence system of the voltages
Adjustable current criterion for undervoltage protection functions
26
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018